TR-1 Fuel- Gas Piping (Welding) (BC 1704.19)
1704.18 High-pressure-gas piping. High-pressure-gas piping regulated in Section 406 of the New York City Fuel Gas Code shall be subject to periodic…
Technical info
Full details ›1704.18 High-pressure-gas piping. High-pressure-gas piping regulated in Section 406 of the New York City Fuel Gas Code shall be subject to periodic special inspection in accordance with this section.
1704.18.1 Welding. The special inspector shall verify the qualifications of the welder, the quality of the welding materials and equipment prior to welding operations. The special inspector shall review the proposed welding procedures for compliance with applicable standards listed in Section 406 of the New York City Fuel Gas Code.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Aluminum Welding (BC 1704.26)
1704.26 Aluminum construction. The special inspections for structural aluminum elements of buildings and structures shall be as required by Section 1704.26.1‡. 1704.26.1…
Technical info
Full details ›1704.26 Aluminum construction. The special inspections for structural aluminum elements of buildings and structures shall be as required by Section 1704.26.1‡.
1704.26.1 Welding operations. All welding operations of aluminum elements shall be subject to special inspection for compliance with this code, AA ASM-35, Parts 1A and 1B of the Aluminum Design Manual, and AWS D1.2.
Exception: Welding operations in connections where the calculated stresses in the welds are less than 50 percent of the basic allowable values.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Chimneys (BC 1704.24)
1704.24 Chimneys. New and altered chimneys shall be subject to special inspection. The chimney shall be inspected to verify compliance with the…
Technical info
Full details ›1704.24 Chimneys. New and altered chimneys shall be subject to special inspection. The chimney shall be inspected to verify compliance with the approved construction documents, and proper clearance or isolation from adjacent combustible construction. Testing of the chimney shall be performed in accordance with Section 810 of the New York City Mechanical Code.
Exception: A pressurized smoke test need not be performed on an existing negative pressure chimney if the lining of such chimney is not affected by alterations and the registered design professional specifies on the approved construction documents that such test does not need to be performed on such chimney.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Concrete – Cast -in -Place (BC 1704.4)
1704.4 Concrete construction. The special inspections and verifications for concrete construction shall be as required by this section and Table 1704.4. Exception:…
Technical info
Full details ›1704.4 Concrete construction. The special inspections and verifications for concrete construction shall be as required by this section and Table 1704.4.
Exception: Special inspections shall not be required for the following when specifically exempted on the approved construction documents:
1. Concrete placement of less than 50 cubic yards (38 m3)‡ provided that the concrete is nonstructural and is not subject to the durability requirements of Section 1904. In such case, testing may be waived by the registered design professional who prepared the structural construction documents.
2. Nonstructural concrete slabs supported directly on the ground, including prestressed slabs on grade, where the effective prestress in the concrete is less than 150 psi (1.03 Mpa).
3. Concrete foundation(s) for lightweight fences and recreational equipment.
4. Concrete patios, site furnishings, garden walls, driveways, sidewalks and similar construction.Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Concrete – Precast (BC 1704.4)
1704.4 Concrete construction. The special inspections and verifications for concrete construction shall be as required by this section and Table 1704.4. Exception:…
Technical info
Full details ›1704.4 Concrete construction. The special inspections and verifications for concrete construction shall be as required by this section and Table 1704.4.
Exception: Special inspections shall not be required for the following when specifically exempted on the approved construction documents:
1. Concrete placement of less than 50 cubic yards (38 m3)‡ provided that the concrete is nonstructural and is not subject to the durability requirements of Section 1904. In such case, testing may be waived by the registered design professional who prepared the structural construction documents.
2. Nonstructural concrete slabs supported directly on the ground, including prestressed slabs on grade, where the effective prestress in the concrete is less than 150 psi (1.03 Mpa).
3. Concrete foundation(s) for lightweight fences and recreational equipment.
4. Concrete patios, site furnishings, garden walls, driveways, sidewalks and similar construction.Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Concrete – Prestressed (BC 1704.4)
1704.4 Concrete construction. The special inspections and verifications for concrete construction shall be as required by this section and Table 1704.4. Exception:…
Technical info
Full details ›1704.4 Concrete construction. The special inspections and verifications for concrete construction shall be as required by this section and Table 1704.4.
Exception: Special inspections shall not be required for the following when specifically exempted on the approved construction documents:
1. Concrete placement of less than 50 cubic yards (38 m3)‡ provided that the concrete is nonstructural and is not subject to the durability requirements of Section 1904. In such case, testing may be waived by the registered design professional who prepared the structural construction documents.
2. Nonstructural concrete slabs supported directly on the ground, including prestressed slabs on grade, where the effective prestress in the concrete is less than 150 psi (1.03 Mpa).
3. Concrete foundation(s) for lightweight fences and recreational equipment.
4. Concrete patios, site furnishings, garden walls, driveways, sidewalks and similar construction.Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Emergency Power Systems (Generators)
1704.13 Special case. Special inspections shall be required for proposed work that is, in the opinion of the commissioner, unusual in its…
Technical info
Full details ›1704.13 Special case. Special inspections shall be required for proposed work that is, in the opinion of the commissioner, unusual in its nature, such as, but not limited to, the following examples:
•Construction materials and systems that are alternatives to materials and systems prescribed by this code.
•Unusual design applications of materials described in this code.
•Materials and systems required to be installed in accordance with additional manufacturer’s instructions that prescribe requirements not contained in this code or in standards referenced by this code.SECTION BC 2702 EMERGENCY POWER SYSTEMS
2702.1 Installation. Emergency systems shall be installed in accordance with the New York City Electrical Code, NFPA 110 and NFPA 111, and shall have an on-premises fuel supply sufficient for not less than 6-hour full-demand operation of the system. However, for R-2 occupancies required to provide emergency power systems pursuant to the provisions of Section 403.11.2, and for voluntarily installed emergency power systems, natural gas from the public utility street main shall be permitted as fuel supply.Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Excavation – Sheeting Shoring Bracing
3304.4 Protection of sides of excavations. 3304.4.1 Shoring, bracing and sheeting. The sides of all excavations, including related or resulting embankments, that…
Technical info
Full details ›3304.4 Protection of sides of excavations.
3304.4.1 Shoring, bracing and sheeting. The sides of all excavations, including related or resulting embankments, that are 5 feet (1524 mm) or greater in depth or height measured from the level of the adjacent ground surface to the deepest point of the excavation shall be protected and maintained by shoring, bracing, sheeting, sheet piling, or by other retaining structures as may be necessary to prevent the sides of the excavation from caving in before permanent supports are provided. Such methods of protection shall be subject to special inspection in accordance with the provisions of Chapter 17.
Alternatively, excavation sides may be sloped not steeper than 45 degrees (0.79 rad)‡ or stepped so that the average slope is not steeper than 45 degrees (0.79 rad)‡ with no step more than 5 feet (1524 mm) high, provided such slope does not endanger any structure, including subsurface structures. Deviation from the foregoing limitations for cut slopes shall be permitted only upon the completion of a soil investigation report acceptable to the commissioner.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Exterior Insulation Finish Systm (BC 1704.12)
1704.12 Exterior insulation and finish systems (EIFS). Special inspections shall be required for all EIFS applications installed more than 15 feet (4572…
Technical info
Full details ›1704.12 Exterior insulation and finish systems (EIFS). Special inspections shall be required for all EIFS applications installed more than 15 feet (4572 mm)‡ above adjacent finished grades.
1704.12.1 The special inspection shall include verification of: compliance with approved construction documents for attachment to structure, installation of waterproofing membranes, weeps, drains, mold prevention features and conformance with the manufacturers’ installation guidelines.
Details
SIGN-ON / Inspect / SIGN-OFF (package
-
TR-1 SPECIAL INSPECTIONS
TR-1 Final Inspection 28-116.2.4.2 BC-109.5 Dir-14
Call for job specific quote. 109.5 Final inspection. Refer to Chapter 1 of Title 28 of the Administrative Code. Directive…
Technical info
Full details ›Call for job specific quote.
109.5 Final inspection. Refer to Chapter 1 of Title 28 of the Administrative Code.
Directive 14 Final inspection is required on all non- CO jobs in NYC as per Bulletin 2018-08.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Fire Alarm Test (BC 907 BC 1704.13)
907.19 Inspection, testing and maintenance. The maintenance and testing schedules and procedures for fire alarm and fire detection systems shall be in…
Technical info
Full details ›907.19 Inspection, testing and maintenance. The maintenance and testing schedules and procedures for fire alarm and fire detection systems shall be in accordance with the New York City Fire Code.
907.16 Acceptance tests. Upon completion of the installation of the fire alarm system, alarm notification appliances and circuits, alarm-initiating devices and circuits, supervisory-signal initiating devices and circuits, signaling line circuits, and primary and secondary power supplies shall be tested in accordance with NFPA 72.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Fire Resistance Rated Construction (BC 110.3.4)
110.3.4 Fire-resistance-rated construction inspection.Fire-resistance-rated construction shall be inspected to determine compliance with the…
Technical info
Full details ›110.3.4 Fire-resistance-rated construction inspection.Fire-resistance-rated construction shall be inspected to determine compliance with the approved construction documents, including inspection of the following work:1.Fire-resistance-rated partitions, floors, ceilings, shafts;and2.Fire shutters.Exception:Where the scope of work affecting an existing fire-rated wall assembly is limited to through-penetration firestopping and, in the course of work, the cutting away or removal of any part of the existing fire-resistance-rated construction becomes necessary in the general area surrounding the penetration, not to exceed 4 square feet (0.37 m2) in any given area, the progress inspection for fire-resistance-rated construction shall not be required provided that the special inspection agency for the through-penetration firestopping special inspection verifies that the removed portion of fire-resistance-rated construction (i) is less than 4 square feet (0.37 m2), and (ii) has been restored to its original condition
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Fire-Resistant Penetrations and Joints BC1704.27
109.3.4 Fire-resistance-rated construction inspection. Fire-resistance-rated construction shall be inspected to determine compliance with the approved construction documents, including inspection of the following…
Technical info
Full details ›109.3.4 Fire-resistance-rated construction inspection. Fire-resistance-rated construction shall be inspected to determine compliance with the approved construction documents, including inspection of the following work:
1. Fire-resistance-rated partitions, floors, ceilings, shafts;
2. Fireblocking of concealed spaces;
3. Through-penetration firestopping, draftstopping and fireblocking;
4. Fire dampers;
5. Fire shutters; and
6. Protection of structural members.Exception: Work regulated and inspected under Chapter 17.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Flood Zone Compliance (BC G105)
109.3.2 lowest floor elevation. In areas of special flood hazzard, upon placement of the lowest floor, including the basement (for flood zone…
Technical info
Full details ›109.3.2 lowest floor elevation. In areas of special flood hazzard, upon placement of the lowest floor, including the basement (for flood zone purposes), and prior to further vertical construction, the elevation report required in item 1 of Section G shall be submitted to the department.
Details
TR-1 Private Onsite Disposal System Inspection
A private (PVT) onsite disposal system is a self-contained sewage treatment and absorption system installed on a property that is not connected — or not yet connected — to the NYC municipal sewer network. While most of New York City’s five boroughs are served by the DEP sewer system, private onsite disposal systems remain in active use on properties in Staten Island, eastern Queens, and areas of Brooklyn where sewer laterals have not been extended, and are also required for certain new construction projects on large or remote lots.
System types covered under this inspection:
- Septic tanks — underground chambers that collect and partially treat sewage before discharging to a soil absorption field
- Cesspools — older pit-based systems that allow liquid waste to seep into the surrounding soil; subject to NYC DEP elimination programs in many areas
- Soil absorption systems (leach fields) — subsurface distribution pipes or chambers that disperse pre-treated effluent into the ground
When a TR-1 Progress Inspection Is Required
A TR-1 PVT onsite disposal system inspection is required by the NYC Department of Buildings when an onsite disposal system is included as part of a new construction or alteration permit. The inspection must be performed before the system is covered or backfilled — once buried, verification of code compliance is no longer possible without excavation.
What EZTR1 Inspects
EZTR1’s certified TR-1 progress inspectors verify the following against the approved DOB construction drawings and NYC Plumbing Code (PC) requirements:
- System location and setback distances — minimum clearances from property lines, foundations, wells, and drainage areas are confirmed on site
- Tank and absorption field sizing — dimensions and capacity match the approved design based on calculated daily sewage flow
- Depth of installation — cover depths comply with the approved drawings and code minimums
- Inlet and outlet pipe connections — proper tee connections, baffle placement, and effluent distribution confirmed before backfill
All inspection findings are documented in the TR-1 progress inspection report filed directly with the NYC Department of Buildings. Inspections are timed to occur at the construction milestone before the system is covered, to avoid costly re-excavation.
Ready to schedule your TR-1 PVT onsite disposal system inspection? Contact EZTR1 to coordinate timing with your plumbing contractor before backfill.
-
TR-1 SPECIAL INSPECTIONS
TR-1 Footing Foundation (BC 109.3.1)
109.3.1 Footing and foundation inspection. Footing and foundation inspections shall be made after excavations for footings are complete and any required reinforcing…
Technical info
Full details ›109.3.1 Footing and foundation inspection. Footing and foundation inspections shall be made after excavations for footings are complete and any required reinforcing steel is in place. For concrete foundations, any required forms shall be in place prior to inspection. Materials for the foundation shall be on the job, except where concrete is ready mixed in accordance with ASTM C 94, the concrete need not be on the job.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Frame Inspection (BC 109.3.3)
109.3.3 Frame inspection. Framing inspections shall be performed to determine compliance with the approved construction documents. Exception: Work regulated and inspected under…
Technical info
Full details ›109.3.3 Frame inspection. Framing inspections shall be performed to determine compliance with the approved construction documents.
Exception: Work regulated and inspected under Chapter 17.
Details
What BC 109.3.3 Frame Inspection Covers
The BC 109.3.3 frame inspection is a required progress inspection under the NYC Building Code that must be completed before any framing is concealed by insulation, sheathing, drywall, or other finish materials. It is distinct from Chapter 17 special inspections — which cover structural steel connections, high-strength bolts, and engineered systems — and applies primarily to wood-frame and light-gauge metal stud construction in 1-, 2-, and 3-family homes, townhouses, and low-rise residential buildings across New York City.
What the inspector verifies:
- Structural member compliance — floor joists, rafters, studs, headers, and bearing walls match the species, size, spacing, and span specified in the approved construction documents
- Connection details — joist hangers, hurricane ties, hold-downs, and shear wall nailing patterns are installed per the approved drawings
- Fireblocking — continuous fireblocking is in place at all required locations per NYC BC Section 718, including between floors, at top and bottom plates, and around openings in stud cavities
- Draftstopping — where required in large attic or crawl-space areas, draftstop partitions are correctly positioned
How EZTR1 Coordinates with the DOB
EZTR1’s TR-1 progress inspectors perform the BC 109.3.3 framing inspection on site, document all findings against the approved drawings, and submit the TR-1 report directly to the NYC Department of Buildings. The inspection is coordinated with the construction schedule to occur at the right framing stage — before any work is covered — ensuring no re-opening of finished assemblies is required.
Ready to schedule your TR-1 frame inspection? Contact EZTR1 to coordinate timing with your general contractor.
-
TR-1 SPECIAL INSPECTIONS
TR-1 Heating Systems 1704.25
1704.25 Through-penetration firestop systems, concealed draftstop and fireblock systems. All through-penetration firestopping, draftstopping and fireblocking shall be subject to periodic special inspection…
Technical info
Full details ›1704.25 Through-penetration firestop systems, concealed draftstop and fireblock systems. All through-penetration firestopping, draftstopping and fireblocking shall be subject to periodic special inspection prior to concealment to determine compliance with the approved construction documents. Listed systems shall be inspected for compliance with their listing.
Exception: Through-penetration firestop systems may be inspected in accordance with ASTM E 2174-04 when authorized by the registered design professional of record and when the contractor applies the procedures established in that standard.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Hi Pressure Steam (Welding) (BC 1704-17)
1704.17 High-pressure-steam piping. High-pressure-steam piping regulated by Section 1210 of the New York City Mechanical Code, shall be subject to special inspection…
Technical info
Full details ›1704.17 High-pressure-steam piping. High-pressure-steam piping regulated by Section 1210 of the New York City Mechanical Code, shall be subject to special inspection in accordance with this section.
1704.17.1 Welding. The special inspector shall verify the qualifications of the welder and the quality of the welding materials and equipment prior to welding operations. The special inspector shall review the proposed welding procedures for compliance with applicable standards listed in Section 1210.4 of the New York City Mechanical Code.1704.17.2 Welding operations. The special inspector shall perform periodic inspection of the pipe joining and welding operations in accordance with the above. Radiographic testing shall be applied to connections as indicated in Section 1210.4.9 of the New York City Mechanical Code. Unacceptable connections and installations shall be rejected.
1704.17.2 Welding operations. The special inspector shall perform periodic inspection of the pipe joining and welding operations in accordance with the above. Radiographic testing shall be applied to connections as indicated in Section 1210.4.9 of the New York City Mechanical Code. Unacceptable connections and installations shall be rejected.
1704.17.3 Testing of high-pressure-steam piping. Hydrostatic testing shall be performed on the completed installation of new and altered systems in accordance with Section 1210.4.10 of the New York City Mechanical Code.
Exception: Testing requirements shall not apply to alteration or repairs to existing high-pressure-steam piping systems in which the integrity of the piping is not affected. Such alterations shall be visually inspected for compliance with the approved construction documents.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 High Temperature Fuel Gas Piping (Welding) (BC 1704.19)
1704.19 High-pressure-gas piping.High-pressure-gas pipingregulated in Section 406 of the New York City FuelGas Codeshall be subject to special inspection in accordance with…
Technical info
Full details ›1704.19 High-pressure-gas piping.High-pressure-gas pipingregulated in Section 406 of the New York City FuelGas Codeshall be subject to special inspection in accordance with this section.Special inspection of seismic bracing shall be performed in accordance with Section 1707.7
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 High Temperature Hot Water Piping (Welding) (BC 1704-18)
1704.17 High-pressure-steam piping. High-pressure-steam piping regulated by Section 1210 of the New York City Mechanical Code, shall be subject to special inspection…
Technical info
Full details ›1704.17 High-pressure-steam piping. High-pressure-steam piping regulated by Section 1210 of the New York City Mechanical Code, shall be subject to special inspection in accordance with this section.
1704.17.1 Welding. The special inspector shall verify the qualifications of the welder and the quality of the welding materials and equipment prior to welding operations. The special inspector shall review the proposed welding procedures for compliance with applicable standards listed in Section 1210.4 of the New York City Mechanical Code.1704.17.2 Welding operations. The special inspector shall perform periodic inspection of the pipe joining and welding operations in accordance with the above. Radiographic testing shall be applied to connections as indicated in Section 1210.4.9 of the New York City Mechanical Code. Unacceptable connections and installations shall be rejected.
1704.17.2 Welding operations. The special inspector shall perform periodic inspection of the pipe joining and welding operations in accordance with the above. Radiographic testing shall be applied to connections as indicated in Section 1210.4.9 of the New York City Mechanical Code. Unacceptable connections and installations shall be rejected.
1704.17.3 Testing of high-pressure-steam piping. Hydrostatic testing shall be performed on the completed installation of new and altered systems in accordance with Section 1210.4.10 of the New York City Mechanical Code.
Exception: Testing requirements shall not apply to alteration or repairs to existing high-pressure-steam piping systems in which the integrity of the piping is not affected. Such alterations shall be visually inspected for compliance with the approved construction documents.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Individual On-Site Private Sewer Disposal System Installation (BC 1704.22)
-
TR-1 SPECIAL INSPECTIONS
TR-1 Lowest Floor Elevation FEMA (BC 109.3.2)
109.3.2 Lowest floor elevation. In areas of special flood hazard, upon placement of the lowest floor, including the basement (for flood zone…
Technical info
Full details ›109.3.2 Lowest floor elevation. In areas of special flood hazard, upon placement of the lowest floor, including the basement (for flood zone purposes), and prior to further vertical construction, the elevation inspection report required in Item 1 of Section G105.3 of Appendix G shall be submitted to the department.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Masonry (BC 1704.5)
1704.5 Masonry construction. Masonry construction shall be inspected and evaluated in accordance with the requirements of this section, depending on the structural…
Technical info
Full details ›1704.5 Masonry construction. Masonry construction shall be inspected and evaluated in accordance with the requirements of this section, depending on the structural occupancy category of the building or structure or nature of occupancy, as defined by this code (see Table 1604.5 and Section 1616.2).
Details
SIGN-ON / Inspect / SIGN-OFF (package
-
TR-1 SPECIAL INSPECTIONS
TR-1 Mastric and Intumescent fire- resistant coatings
1704.12 Exterior insulation and finish systems (EIFS). Special inspections shall be required for all EIFS applications installed more than 15 feet (4572…
Technical info
Full details ›1704.12 Exterior insulation and finish systems (EIFS). Special inspections shall be required for all EIFS applications installed more than 15 feet (4572 mm)‡ above adjacent finished grades.
1704.12.1 The special inspection shall include verification of: compliance with approved construction documents for attachment to structure, installation of waterproofing membranes, weeps, drains, mold prevention features and conformance with the manufacturers’ installation guidelines.
Details
SIGN-ON / Inspect / SIGN-OFF (package
-
TR-1 SPECIAL INSPECTIONS
TR-1 Mechanical Demolition (BC 1704.19 BC 3306.6)
1704.19 Structural safety during construction operations. Construction work consisting of structural alterations, excavation, underpinning, and demolition work that requires “design” as defined…
Technical info
Full details ›1704.19 Structural safety during construction operations. Construction work consisting of structural alterations, excavation, underpinning, and demolition work that requires “design” as defined in Chapter 33, including earth shoring, underpinning, protection of adjacent structures and buildings, shall be subject to special inspection in accordance with this section. All alterations to existing structures in which loads are transferred from one structural system of structural elements to another, such as installation of columns or girders, replacement of existing bearing walls, the creation of openings or slots in existing walls, girders or floors, alteration of arches, rigid frames, trusses in frame buildings, or where the stability or integrity of a structural system is to be temporarily diminished shall be subject to special inspections in accordance with this section.
Exception: Construction operations not requiring “design” as defined in Chapter 33.
3306.6 Special inspection. Where mechanical demolition equipment, other than handheld devices, is to be used in the full or partial demolition of a building from within the building, or is to be used within the building to remove debris or move material, such demolition operation shall be subject to special inspection in accordance with the provisions of Chapter 17. The special inspector shall visit the site a minimum of three times: before demolition operations start, during demolition, and at the conclusion of demolition.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Mechanical Systems (BC 1704.15)
1704.15 Special inspection for mechanical systems. Mechanical systems regulated by Sections 107 and 507 and Chapters 10, 11 and 12 of the…
Technical info
Full details ›1704.15 Special inspection for mechanical systems. Mechanical systems regulated by Sections 107 and 507 and Chapters 10, 11 and 12 of the New York City Mechanical Code shall be inspected for conformance with the approved construction documents.
Details
Sign on / Inspect / S-OFF (package) Including preparation of up to 3 Equipment Use Cards
-
TR-1 SPECIAL INSPECTIONS
TR-1 Pier Foundations (BC1704.9)
1704.9 Pier foundations. Special inspection is required for all pier foundations designed in accordance with Section 1808.2.2.‡ Exception: Piers for support of…
Technical info
Full details ›1704.9 Pier foundations. Special inspection is required for all pier foundations designed in accordance with Section 1808.2.2.‡
Exception: Piers for support of lightweight fences, recreational equipment, site furnishings and similar construction, unless special inspection is specifically noted as required on the approved construction documents
Details
-
-
TR-1 SPECIAL INSPECTIONS
TR-1 Preliminary (28-116.2.1, BC 109.2)
109.2 Preliminary inspection. Refer to Chapter 1 of Title 28 of the Administrative Code.
Technical info
Full details ›109.2 Preliminary inspection. Refer to Chapter 1 of Title 28 of the Administrative Code.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Private On-site Storm Water Drainage Disposal Systems and Detention Facilit
1704.21.1.2 Soil percolation tests.Prior to the approval of construction documents, soil percolation tests shall be performed in accordance with the provisions of…
Technical info
Full details ›1704.21.1.2 Soil percolation tests.Prior to the approval of construction documents, soil percolation tests shall be performed in accordance with the provisions of Section 1114.2.2 of the New York City Plumbing Code at the site of a proposed on-site stormwater drainage and detention facility installation to determine the suitability of the soil and site. Such test shall beperformed under the supervision of a special inspector. The results of the percolation tests shall be filed on forms provided by the department, stating the suitability of the site and the capacity of the subsoil for the proposed use. The registered design professional of record for the dry-well system shall benotified immediately if the results of the percolation test demonstrate that the system may not function as designed
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Public Assembly Emergency Lighting
Public Assembly Emergency Lighting (28-116.2.2)Compliance inspections. In addition to the inspections specified in this code, the commissioner is authorized to make or…
Technical info
Full details ›Public Assembly Emergency Lighting (28-116.2.2)
Compliance inspections. In addition to the inspections specified in this code, the commissioner is authorized to make or require other inspections of any construction work to ascertain compliance with the provisions of this code and other laws that are enforced by the department.Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 PVT Onsite Disposal System
TR-1 Private Onsite Disposal System Inspection A private (PVT) onsite disposal system is a self-contained sewage […]
Technical info
Full details ›Details
TR-1 Private Onsite Disposal System Inspection
A private (PVT) onsite disposal system is a self-contained sewage treatment and absorption system installed on a property that is not connected — or not yet connected — to the NYC municipal sewer network. While most of New York City’s five boroughs are served by the DEP sewer system, private onsite disposal systems remain in active use on properties in Staten Island, eastern Queens, and areas of Brooklyn where sewer laterals have not been extended, and are also required for certain new construction projects on large or remote lots.
System types covered under this inspection:
- Septic tanks — underground chambers that collect and partially treat sewage before discharging to a soil absorption field
- Cesspools — older pit-based systems that allow liquid waste to seep into the surrounding soil; subject to NYC DEP elimination programs in many areas
- Soil absorption systems (leach fields) — subsurface distribution pipes or chambers that disperse pre-treated effluent into the ground
When a TR-1 Progress Inspection Is Required
A TR-1 PVT onsite disposal system inspection is required by the NYC Department of Buildings when an onsite disposal system is included as part of a new construction or alteration permit. The inspection must be performed before the system is covered or backfilled — once buried, verification of code compliance is no longer possible without excavation.
What EZTR1 Inspects
EZTR1’s certified TR-1 progress inspectors verify the following against the approved DOB construction drawings and NYC Plumbing Code (PC) requirements:
- System location and setback distances — minimum clearances from property lines, foundations, wells, and drainage areas are confirmed on site
- Tank and absorption field sizing — dimensions and capacity match the approved design based on calculated daily sewage flow
- Depth of installation — cover depths comply with the approved drawings and code minimums
- Inlet and outlet pipe connections — proper tee connections, baffle placement, and effluent distribution confirmed before backfill
All inspection findings are documented in the TR-1 progress inspection report filed directly with the NYC Department of Buildings. Inspections are timed to occur at the construction milestone before the system is covered, to avoid costly re-excavation.
Ready to schedule your TR-1 PVT onsite disposal system inspection? Contact EZTR1 to coordinate timing with your plumbing contractor before backfill.
-
TR-1 SPECIAL INSPECTIONS
TR-1 Raising and Moving of a Building (BC 1704.20.5)
TR-1 Building Raising and Moving Inspection Raising and moving a building is one of the most […]
Technical info
Full details ›Details
TR-1 Building Raising and Moving Inspection
Raising and moving a building is one of the most dramatic operations in urban construction — and one of the most tightly regulated under the NYC Building Code. Under BC Section 1704.20.5, any work involving the physical elevation or relocation of a building requires a special inspection by a registered agency throughout the operation. EZTR1 provides TR-1 progress inspections for building-raising and moving projects across all five boroughs.
What triggers a BC 1704.20.5 inspection?
A NYC DOB permit for raising or moving a building is required whenever:
- A structure is lifted off its existing foundation to allow underpinning, foundation replacement, or the addition of a new basement or cellar level
- A building is elevated to meet FEMA Base Flood Elevation (BFE) requirements — a common post-Sandy compliance project in the Rockaways (Queens), Staten Island waterfront neighborhoods, Red Hook (Brooklyn), and Gerritsen Beach
- An existing building is physically relocated on the same lot or to an adjacent parcel — common in landmarked historic preservation projects and lot-consolidation scenarios
How Building Raising Works in NYC
The raising process uses synchronized hydraulic jacks placed at strategic points beneath the building’s sill plate, foundation walls, or steel grillage. The structure is incrementally lifted — typically in increments of a few inches at a time — while temporary cribbing (stacked timber or steel blocking) is inserted beneath the building to maintain stability between jack cycles. For relocation, the raised building is then placed on wheeled dollies or rollers and moved along a prepared pathway to its new position.
What EZTR1 Inspects Under BC 1704.20.5
EZTR1’s TR-1 progress inspectors monitor the following throughout the raising or moving operation:
- Jack placement and load distribution — confirmed against the approved engineering documents before lifting commences
- Incremental lift verification — each lift cycle is documented to confirm the building is rising uniformly without differential settlement or structural distress
- Cribbing adequacy and stability — temporary support systems are verified to be adequate for the imposed loads at each stage
- Foundation condition — before the building is set down on its new or modified foundation, the inspector confirms the receiving surface meets the approved design
All findings are documented in the TR-1 special inspection report submitted to the NYC Department of Buildings.
Ready to schedule your BC 1704.20.5 building-raising inspection? Contact EZTR1 to coordinate with your lifting contractor before work begins.
-
TR-1 SPECIAL INSPECTIONS
TR-1 Seismic Isolation Systems (BC 1707.8)
1707.8 Seismic isolation system. There shall be periodic special inspection during the fabrication and installation of isolator units and energy dissipation devices…
Technical info
Full details ›1707.8 Seismic isolation system. There shall be periodic special inspection during the fabrication and installation of isolator units and energy dissipation devices if used as part of the seismic isolation system.
1710.1 Conformance to standards. The design strengths and permissible stresses of any structural material that are identified by a manufacturer’s designation as to manufacture and grade by mill tests, or the strength and stress grade is otherwise confirmed to the satisfaction of the commissioner shall conform to the specifications and methods of design of accepted engineering practice or the rules of the department in the absence of applicable standards.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Septic System Installation
1704.20 Site storm drainage disposal and detention facilities. Storm water detention facilities, roof retention facilities and dry-well systems shall be inspected for…
Technical info
Full details ›1704.20 Site storm drainage disposal and detention facilities. Storm water detention facilities, roof retention facilities and dry-well systems shall be inspected for conformance with the approved construction documents. Minor variations, based on actual site conditions, shall be acceptable at the discretion of the registered design professional of record. Verification shall include:
1. Materials of construction.
2. Bedding of pipe and facilities.
3. Placement and installation of fill materials.
4. Volume of drywell and detention facilities.
5. Installation of volume flow control devices.
6. Workmanship and quality of installation.
7. Overall conformance with the approved construction documents. Hydrostatic testing of the detention system shall be required when the system is designed as watertight.Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Site Storm Drainage Disposal Detention Syste
1704.20 Site storm drainage disposal and detention facilities. Storm water detention facilities, roof retention facilities and dry-well systems shall be inspected for…
Technical info
Full details ›1704.20 Site storm drainage disposal and detention facilities. Storm water detention facilities, roof retention facilities and dry-well systems shall be inspected for conformance with the approved construction documents. Minor variations, based on actual site conditions, shall be acceptable at the discretion of the registered design professional of record. Verification shall include:
1. Materials of construction.
2. Bedding of pipe and facilities.
3. Placement and installation of fill materials.
4. Volume of drywell and detention facilities.
5. Installation of volume flow control devices.
6. Workmanship and quality of installation.
7. Overall conformance with the approved construction documents. Hydrostatic testing of the detention system shall be required when the system is designed as watertightDetails
-
TR-1 SPECIAL INSPECTIONS
TR-1 Smoke Control Systems (BC 1704.14)
1704.14 Special inspection for smoke control. Smoke control systems shall be tested by a special inspector in accordance with Sections 1704.14.1 and…
Technical info
Full details ›1704.14 Special inspection for smoke control. Smoke control systems shall be tested by a special inspector in accordance with Sections 1704.14.1 and 909.
1704.14.1 Testing scope. The test scope shall be as follows:
1. During erection of ductwork and prior to concealment for the purposes of leakage testing and recording of device location.
2. Prior to occupancy and after sufficient completion for the purposes of pressure difference testing, flow measurements and detection and control verification.Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Soil Percolation Test- Drywell (BC 1704.20.1)
1704.20.1 Soil percolation tests. Soil percolation tests shall be performed at the site of a proposed individual on-site private sewage disposal system…
Technical info
Full details ›1704.20.1 Soil percolation tests. Soil percolation tests shall be performed at the site of a proposed individual on-site private sewage disposal system installation to determine the suitability of the soil and site. Such test shall be performed under the supervision of a special inspector. The results of the percolation tests shall be filed on forms provided by the department, stating the suitability of the site and the capacity of the subsoil for the proposed use. The registered design professional of record for the dry-well system shall be notified immediately if the results of the percolation test demonstrate that the approved system may not function as designed.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Soil Percolation Test- Septic (BC 1704.20.1)
1704.20.1 Soil percolation tests. Soil percolation tests shall be performed at the site of a proposed individual on-site private sewage disposal system…
Technical info
Full details ›1704.20.1 Soil percolation tests. Soil percolation tests shall be performed at the site of a proposed individual on-site private sewage disposal system installation to determine the suitability of the soil and site. Such test shall be performed under the supervision of a special inspector. The results of the percolation tests shall be filed on forms provided by the department, stating the suitability of the site and the capacity of the subsoil for the proposed use. The registered design professional of record for the dry-well system shall be notified immediately if the results of the percolation test demonstrate that the approved system may not function as designed.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Soils- Site Preperation (BC 1704.7.1)
1704.7 Soils. The special inspections for existing site soil conditions, fill placement and load-bearing requirements shall be performed in accordance with Sections…
Technical info
Full details ›1704.7 Soils. The special inspections for existing site soil conditions, fill placement and load-bearing requirements shall be performed in accordance with Sections 1704.7.1 through 1704.7.3. The approved soils report, required by Section 1802.2, shall be used to determine compliance.
Details
SIGN-ON / Inspect / SIGN-OFF (package
-
TR-1 SPECIAL INSPECTIONS
TR-1 Sprayed Fire Resistant Materials (BC 1704.11)
1704.11 Sprayed fire-resistant materials. Special inspections for sprayed fire-resistant materials applied to structural elements and decks shall be in accordance with Sections…
Technical info
Full details ›1704.11 Sprayed fire-resistant materials. Special inspections for sprayed fire-resistant materials applied to structural elements and decks shall be in accordance with Sections 1704.11.1 through 1704.11.5. Special inspections shall be based on the fire-resistance design as designated in the approved construction documents.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Sprinkler Systems (BC 1704.21)
1704.21 Sprinkler system special inspection. New and altered sprinkler system systems shall be inspected in accordance with Section Sections 903 and 1704.21.1.…
Technical info
Full details ›1704.21
Sprinkler system special inspection. New and altered sprinkler system systems shall be inspected in accordance with Section Sections 903 and 1704.21.1. The permit holder responsible for the sprinkler work shall perform all required acceptance tests, complete and sign the appropriate contractor’s material and test certifications. The special inspector shall witness all required tests, and shall verify that all installations of all materials, fittings, hangers, assemblies and signage are in accordance with the approved construction documents, that painting of the sprinkler system required by Section 903.6 of this code has been performed and that the contractor has transmitted required maintenance literature and instruction to the owner. The special inspector shall verify that the material and test certification forms have been transmitted to the Fire Department and the Department of Buildings‡.Exception: Special inspection of The special inspector need not witness the hydrostatic pressure test shall not be required when such test is witnessed by the department.
1704.21.1 Hydrostatic pressure testing. All new or altered sprinkler systems in buildings shall undergo successful hydrostatic pressure testing by a licensed master plumber or licensed fire suppression piping contractor in accordance with the requirements of this code, including Section 901.5, and NFPA 13.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Standpipe Systems (BC 1704.22)
1704.22 Standpipe system special inspection. New and altered standpipe systems shall be inspected in accordance with Section Sections 905 and 1704.22.1. The…
Technical info
Full details ›1704.22 Standpipe system special inspection. New and altered standpipe systems shall be inspected in accordance with Section Sections 905 and 1704.22.1. The permit holder responsible for the standpipe work shall perform all required acceptance tests, and complete and sign the appropriate contractor’s material and test certifications. The special inspector shall witness all required tests, verify that installation of all materials, fittings, hangers, assemblies and signage are in accordance with the approved construction documents, that painting of the standpipe system required by Section 905.11 of this code has been performed and that the contractor has transmitted required maintenance literature and instruction to the owner. The special inspector shall verify that the material and test certification forms have been transmitted to the Fire Department and the Department of Buildings‡.
Exception: Special inspection of The special inspector need not witness the hydrostatic pressure test shall not be required when such test is witnessed by the department.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Structural Cold formed Steel (BC 1704.3.4)
1704.3.4 Cold-formed steel construction. Cold-formed steel used structurally shall be subject to the special inspection requirements of Section 1704.3 and Table 1704.3.…
Technical info
Full details ›1704.3.4 Cold-formed steel construction. Cold-formed steel used structurally shall be subject to the special inspection requirements of Section 1704.3 and Table 1704.3. In addition, the following requirements shall be inspected for compliance by the special inspector:
1. The special inspector shall check for compliance with the requirements of Section 2209.1.3.
2. Temporary bracing, shoring, jacks, etc., shall not be removed until the special inspector determines that they are no longer needed.Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Structural Safety-Stability (BC 1704.19)
1704.19 Structural safety during construction operations. Construction work consisting of structural alterations, excavation, underpinning, and demolition work that requires “design” as defined…
Technical info
Full details ›1704.19 Structural safety during construction operations. Construction work consisting of structural alterations, excavation, underpinning, and demolition work that requires “design” as defined in Chapter 33, including earth shoring, underpinning, protection of adjacent structures and buildings, shall be subject to special inspection in accordance with this section. All alterations to existing structures in which loads are transferred from one structural system of structural elements to another, such as installation of columns or girders, replacement of existing bearing walls, the creation of openings or slots in existing walls, girders or floors, alteration of arches, rigid frames, trusses in frame buildings, or where the stability or integrity of a structural system is to be temporarily diminished shall be subject to special inspections in accordance with this section.
Exception: Construction operations not requiring “design” as defined in Chapter 33.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Structural Steel Erecting and Bolting
1704.3.2 Details. The special inspector shall perform an inspection of the steel frame to verify compliance with the details shown on the…
Technical info
Full details ›1704.3.2 Details. The special inspector shall perform an inspection of the steel frame to verify compliance with the details shown on the approved construction documents, such as bracing, stiffening, member locations and proper application of joint details at each connection, including connections designed for seismic effects.
1704.3.3 High-strength bolts. Installation of high-strength bolts shall be inspected in accordance with this section.
1704.3.3.1 General. While the work is in progress, the special inspector shall determine that the requirements for bolts, nuts, washers and paint; bolted parts and installation and tightening in such standards are met. For bolts requiring pretensioning, the special inspector shall observe the preinstallation testing and calibration procedures when such procedures are required by the installation method or by project plans or specifications; determine that all plies of connected materials have been drawn together and properly snugged and monitor the installation of bolts to verify that the selected procedure for installation is properly used to tighten bolts. For joints required to be tightened only to the snug-tight condition, the special inspector need only verify that the connected materials have been drawn together and properly snugged.
1704.3.3.2 Periodic monitoring. Monitoring of bolt installation for pretensioning is permitted to be performed on a periodic basis when using the turn-of-nut method with matchmarking techniques, the direct tension indicator method or the alternate design fastener (twist-off bolt) method. Joints designated as snug tight need be inspected only on a periodic basis.
1704.3.3.3 Continuous monitoring. Monitoring of bolt installation for pretensioning using the calibrated wrench method or the turn-of-nut method without matchmarking shall be performed on a continuous basis.
Details
What Structural Steel Special Inspection Looks
On a busy New York City high-rise construction site, structural steel erection can advance several floors per week. EZTR1’s certified special inspectors are on the steel deck alongside the ironworkers — verifying each bolted connection as it is assembled, before the work is covered by the next floor or fireproofing is applied.
Typical NYC projects that require this inspection:
- High-rise residential towers in Manhattan, Long Island City, and Downtown Brooklyn — where moment frames, braced frames, and composite floor systems require continuous or periodic bolt monitoring
- Mixed-use commercial/residential buildings (5–40+ stories) subject to NYC BC Chapter 17 special inspection requirements from the first structural steel connection
- Additions and structural steel transfers in existing buildings — including cantilever additions and steel moment frame insertions in landmarked buildings
Why it matters: An improperly pretensioned high-strength bolt can slip under wind or seismic load, potentially causing a joint to lose its designed stiffness. NYC’s seismic design requirements mean that many steel connections must be verified as fully pretensioned — not just snug-tight — before the structure is loaded.
EZTR1’s Inspector Qualifications
EZTR1’s structural steel special inspectors hold ICC Special Inspector certifications for structural steel and are registered with the NYC Department of Buildings as qualified special inspection agencies under 1 RCNY § 101-06. Every inspection report is prepared, signed, and submitted directly to the DOB.
Ready to schedule your structural steel special
inspection? Contact EZTR1 to confirm availability for your project’s erection schedule.
-
TR-1 SPECIAL INSPECTIONS
TR-1 Structural Steel – Welding BC 1704.3.1
VERIFICATION AND INSPECTION CONTINUOUS PERIODIC REFERENCED STANDARDa BC REFERENCE 1. Material verification of high-strength bolts, nuts and washers: a. Identification markings to…
Technical info
Full details ›VERIFICATION AND INSPECTION CONTINUOUS PERIODIC REFERENCED
STANDARDa BC REFERENCE1. Material verification of high-strength bolts, nuts and washers:
a. Identification markings to conform to ASTM standards specified in the approved construction documents.
Applicable ASTM material specifications; AISC 335, Section A3.4; AISC LRFD, Section A3.3 —
b. Manufacturer’s certificate of compliance required.2. Inspection of high-strength bolting:
a. Bearing-type connections.
Note b AISC LRFD Section M2.5 1704.3.3
b. Slip-critical connections.3. Material verification of structural steel:
a. Identification markings to conform to ASTM standards specified in the approved construction documents.
— — ASTM A 6 or ASTM A 568 1708.4
b. Manufacturers’ certified mill test reports.— — ASTM A 6 or ASTM A 568
4. Material verification of weld filler materials:
a. Identification markings to conform to AWS specification in the approved construction documents.
— — AISC, ASD, Section A3.6;
AISC LRFD, Section A3.5 —
b. Manufacturer’s certificate of compliance required.5. Inspection of welding:
a. Structural steel:
1) Complete and partial penetration groove welds.
AWS D1.1 1704.3.1
2) Multipass fillet welds.
3) Single—pass fillet welds > 5/16″
4) Single-pass fillet welds ≤ 5/16″
5) Floor and roof deck welds.
— X AWS D1.3 —
b. Reinforcing steel:
— — AWS D1.4
ACI 318: 3.5.2 1903.5.2
1) Verification of weldability of reinforcing steel other than ASTM A 706.
2) Reinforcing steel-resisting flexural and axial forces in intermediate and special moment frames, and boundary elements of special reinforced concrete shear walls and shear reinforcement.
3) Shear reinforcement.
Note a —
4) Other reinforcing steel.6. Inspection of steel frame joint details for compliance with approved constructio
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Structural Steel-Details
1704.3.2 Details. The special inspector shall perform an inspection of the steel frame to verify compliance with the details shown on the…
Technical info
Full details ›1704.3.2 Details. The special inspector shall perform an inspection of the steel frame to verify compliance with the details shown on the approved construction documents, such as bracing, stiffening, member locations and proper application of joint details at each connection, including connections designed for seismic effects.
1704.3.3 High-strength bolts. Installation of high-strength bolts shall be inspected in accordance with this section.
1704.3.3.1 General. While the work is in progress, the special inspector shall determine that the requirements for bolts, nuts, washers and paint; bolted parts and installation and tightening in such standards are met. For bolts requiring pretensioning, the special inspector shall observe the preinstallation testing and calibration procedures when such procedures are required by the installation method or by project plans or specifications; determine that all plies of connected materials have been drawn together and properly snugged and monitor the installation of bolts to verify that the selected procedure for installation is properly used to tighten bolts. For joints required to be tightened only to the snug-tight condition, the special inspector need only verify that the connected materials have been drawn together and properly snugged.
1704.3.3.2 Periodic monitoring. Monitoring of bolt installation for pretensioning is permitted to be performed on a periodic basis when using the turn-of-nut method with matchmarking techniques, the direct tension indicator method or the alternate design fastener (twist-off bolt) method. Joints designated as snug tight need be inspected only on a periodic basis.
1704.3.3.3 Continuous monitoring. Monitoring of bolt installation for pretensioning using the calibrated wrench method or the turn-of-nut method without matchmarking shall be performed on a continuous basis.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Structural Wood Frame Inspection (BC110.3.3)
110.3.3 Frame inspection. Framing inspections shall be performed to determine compliance with the approved construction documents. Exception: Work regulated and inspected under…
Technical info
Full details ›110.3.3 Frame inspection. Framing inspections shall be performed to determine compliance with the approved construction documents.
Exception: Work regulated and inspected under Chapter 17.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Subgrade Inspection (BC 1704.7.1
1704.7.1 Subgrade inspection.Immediately prior to placement of the footings, foundations, fill or other supporting materials the special inspector shall determine that the…
Technical info
Full details ›1704.7.1 Subgrade inspection.Immediately prior to placement of the footings, foundations, fill or other supporting materials the special inspector shall determine that the site has been preparedand isin accordance with the approved geotechnical report
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Subsurface Conditions-Fill Placement & In-Place Density (BC 1704.7.2-3)
1704.7.1 Subgrade inspection.Immediately prior to placement of the footings, foundations, fill or other supporting materials the special inspector shall determine that the…
Technical info
Full details ›1704.7.1 Subgrade inspection.Immediately prior to placement of the footings, foundations, fill or other supporting materials the special inspector shall determine that the site has been preparedand isin accordance with the approved geotechnical report
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Underpinning (BC 1704.9.1)
1704.9.1 Underpinning operations. Special inspection is required for underpinning operations in accordance with Sections 1704.19 and 1814.
Technical info
Full details ›1704.9.1 Underpinning operations. Special inspection is required for underpinning operations in accordance with Sections 1704.19 and 1814.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Vertical Masonry Foundation Elements (BC 1704.9)
TR-1 Vertical Masonry Foundation Elements Vertical masonry foundation elements are a required special inspection category under […]
Technical info
Full details ›Details
TR-1 Vertical Masonry Foundation Elements
Vertical masonry foundation elements are a required special inspection category under NYC Building Code Section 1704.9, applying to new construction where concrete masonry units (CMU), brick, or other masonry materials are used in load-bearing foundation walls, basement walls, party walls, or below-grade structural elements. Unlike wood or steel framing inspections, BC 1704.9 masonry inspection is a Chapter 17 special inspection — meaning it must be performed by a registered special inspection agency such as EZTR1, not simply a DOB progress inspector.
Where this inspection applies in NYC construction
Vertical masonry foundation inspections are most commonly required in:
- Brooklyn and Manhattan brownstone and row house construction — where CMU block or structural brick forms the bearing wall system from the foundation up
- Low-rise mixed-use buildings — where CMU foundation walls and party walls are specified in the approved structural drawings
- New high-rise foundation systems — where masonry retaining or foundation walls are used in below-grade construction on constrained urban sites
What EZTR1 Inspects Under BC 1704.9
EZTR1’s certified special inspectors verify masonry construction at each required inspection stage:
- Masonry unit placement — units are set in conformance with the approved drawings for wall thickness, coursing height, and bond pattern
- Mortar joint thickness and consistency — joints are within the specified range and fully bedded
- Grout pour and lift heights — grout is placed in lifts not exceeding code-specified maximums per the approved mix design
- Reinforcing bar placement — vertical and horizontal rebar is positioned, sized, and spaced per the structural drawings before grouting occurs
- Wall height and alignment — walls are plumb and dimensionally compliant with approved documents at each inspection level
Common Deficiencies Found
The most frequent findings in NYC masonry inspections include improper grout consolidation in CMU cores, rebar displaced from specified location before grouting, and mortar joint thickness outside the ⅜”–⅝” range required by BC 2104.
All findings are documented in the TR-1 special inspection report filed directly with the NYC Department of Buildings.
Ready to schedule your BC 1704.9 masonry special inspection? Contact EZTR1 to coordinate with your masonry contractor.
-
TR-1 SPECIAL INSPECTIONS
TR-1 Wall Panels Curtain Walls and Veneers
1704.10.1 Special inspection for wall panels, curtain walls and veneers. The special inspector shall become familiar with and retain a copy of…
Technical info
Full details ›1704.10.1 Special inspection for wall panels, curtain walls and veneers. The special inspector shall become familiar with and retain a copy of the construction documents, shop drawings, instructions for the sequence of component installation, samples and/or mock-ups, if supplied. The special inspector shall field check the site conditions at the time the structure is prepared for component installation to verify: that the supporting structure is properly aligned and within deign tolerances, that required inserts are properly installed, that framing components are properly sized, aligned, and without structural defects or weakness, that anchors are properly placed, welded, bolted and finished as applicable, that weeps, flashings and tubes are in place and properly drained, that joinery and end dams are properly sealed per plans, that sealing materials with sufficient elongation capability are provided, that gaskets meet specifications, that materials are installed to compensate for horizontal and vertical movement in accordance with the design and the manufacturers’ guidelines and that any other observations pertinent to safety of performance of the wall system have been performed.
1704.10.2 Unsafe wall conditions. The special inspector shall report any immediate hazards to the department.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Wood Install of Pre- Fabricated I – joist
1704.6.4 Prefabricated wood I-joists. The fabrication of prefabricated wood I-joists shall be subject to special inspections in accordance with Section 1704.2 and…
Technical info
Full details ›1704.6.4 Prefabricated wood I-joists. The fabrication of prefabricated wood I-joists shall be subject to special inspections in accordance with Section 1704.2 and the requirements of Section 2303.12.
1704.6.4.1 Erection. The use of prefabricated wood I-joists shall be subject to special inspection for compliance with the approved construction documents, the requirements of Section 1704.1, and the following:
1. All installed materials shall be clean, straight, and otherwise undamaged. Members and parts shall not be stretched, bent, or otherwise distorted unless such forming is in the integral part of the design. The special inspector shall ensure that damaged members are not used for construction.
2. Profiles of members used structurally shall conform to the dimensions specified in the approved construction documents. The installation shall be inspected for compliance with the approved construction documents regarding locations, positions, beam separators, bearing surfaces, fasteners, screws, bolts and bracing, as applicable.
3. The size, location, and number of penetrations shall be inspected for compliance with the approved construction documents and manufacturer’s instructions.
4. Temporary bracing, shoring, jacks, etc., shall not be removed until the special inspector determines that they are no longer needed.Details
SIGN-ON / Inspect / SIGN-OFF (package
-
TR-1 SPECIAL INSPECTIONS
TR-1 Wood – Instal. of Hi Load Diaphr (BC1704.6.1)
1704.6.1 Fabrication of high-load diaphragms. High-load diaphragms using values from Table 2306.3.2 shall be installed with special inspections as indicated in Section…
Technical info
Full details ›1704.6.1 Fabrication of high-load diaphragms. High-load diaphragms using values from Table 2306.3.2 shall be installed with special inspections as indicated in Section 1704.1. The special inspector shall inspect the wood structural panel sheathing to ascertain whether it is of the grade and thickness shown on the approved construction documents. Additionally, the special inspector must verify the nominal size of framing members at adjoining panel edges, the nail or staple diameter and length, the number of fastener lines and that spacing between fasteners in each line and at edge margins agrees with the approved construction documents.
Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Wood Instal of Metal Pl Connected Trusses
1704.6.3 Metal plate connected wood trusses. In addition to the requirements of Section 1704.1, metal-plate-connected wood trusses shall be subject to special…
Technical info
Full details ›1704.6.3 Metal plate connected wood trusses. In addition to the requirements of Section 1704.1, metal-plate-connected wood trusses shall be subject to special inspection in accordance with Section 1704.6.3.1.
1704.6.3.1 Erection. The use of all metal-plate-connected wood trusses shall be subject to special inspection for compliance with the approved construction documents, the requirements of Section 1704.1, and the following:
1. All installed materials shall be clean, straight, and otherwise undamaged. Members and parts shall not be stretched, bent, or otherwise distorted unless such forming is in the integral part of the design. The special inspector shall ensure that damaged members are not used for construction.
2. Profiles of members used structurally shall conform to the dimensions specified in the approved construction documents. The installation shall be inspected for compliance with the approved construction documents regarding locations, positions, beam separators, bearing surfaces, fasteners, screws, bolts and bracing, as applicable.
3. Temporary bracing, shoring, jacks, etc., shall not be removed until the special inspector determines that they are no longer needed.
4. Where prefabricated metal-plate-connected wood trusses are utilized, such prefabricated wood structural elements and assemblies shall also comply with Section 1704.2. Where any metal-plate connectors are utilized in site-built assemblies, such connections and assemblies shall be subject to special inspection for compliance with the requirements of the approved construction documents and manufacturers’ instructions.Details
-
TR-1 SPECIAL INSPECTIONS
TR-1 Wood Off Site Fabr Elements (BC1704.6)
1704.6 Wood construction. Special inspections of the fabrication process of prefabricated wood structural elements and assemblies shall be in accordance with Section…
Technical info
Full details ›1704.6 Wood construction. Special inspections of the fabrication process of prefabricated wood structural elements and assemblies shall be in accordance with Section 1704.2. Special inspections of site-built assemblies shall be in accordance with Section 1704.1.
Details
-
TR-2 CONCRETE SAMPLING AND TESTING
TR-2 Concrete test Cylinders (BC 1905.6)
PLEASE NOTE A TR-2 FORM IS REQUIRED FOR THIS PROJECT1905.6 Evaluation and acceptance of concrete. The criteria for evaluation and acceptance of…
Technical info
Full details ›PLEASE NOTE A TR-2 FORM IS REQUIRED FOR THIS PROJECT
1905.6 Evaluation and acceptance of concrete. The criteria for evaluation and acceptance of concrete shall be as specified in Sections 1905.6.2 through 1905.6.5.5.1905.6.2 Frequency of testing. The frequency of conducting strength tests of concrete shall be as specified in Sections 1905.6.2.1 through 1905.6.2.4.
1905.6.2.1 Minimum frequency. Samples for strength tests of each class of concrete placed each day shall be taken not less than once a day, nor less than once for each 50 cubic yards (38 m3) of concrete nor less than once for each 5,000 square feet (465 m2) of surface area for slabs or walls. For concrete mixes proportioned for durability requirements specified in Section 1904, the registered design professional of record shall specify additional field testing of the concrete for unit weight, air and water content. At the discretion of the registered design professional of record, the frequency of testing may be reduced, but not less than once for each 150 cubic yards (115 m3).1905.6.2 Frequency of testing. The frequency of conducting strength tests of concrete shall be as specified in Sections 1905.6.2.1 through 1905.6.2.4.
1905.6.2.2 Minimum number. On a given project, if the total volume of concrete is such that the frequency of testing required by Section 1905.6.2.1 would provide less than five strength tests for a given class of concrete, tests shall be made from at least five randomly selected batches or from each batch if fewer than five batches are used.
1905.6.2.3 Small volume. When the total volume of a given class of concrete is less than 50 cubic yards (38 m3), and the concrete is nonstructural and is not subject to the durability requirements of Section 1904, testing may be waived by the registered design professional of record.
-
TR-3 CONCRETE DESIGN MIX
TR-3 Concrete Design Mix (BC 1905.3)
PLEASE NOTE A TR-3 FORM IS REQUIRED FOR THIS PROJECT.1905.3 Proportioning on the basis of field experience and/or trial mixtures. Concrete proportioning…
Technical info
Full details ›PLEASE NOTE A TR-3 FORM IS REQUIRED FOR THIS PROJECT.
1905.3 Proportioning on the basis of field experience and/or trial mixtures. Concrete proportioning determined on the basis of field experience or trial mixtures shall be done in accordance with ACI 318, Section 5.3. If the required f’ c is obtained for trial batch mixes prior to the date specified, the trial mix design may be approved. All mixes shall be approved by the registered design professional of record. prior to construction.
-
TR-4 SOIL INVESTIGATION
TR-4 Soils (Boring Test Pits) (BC 1704.7.4)
PLEASE NOTE A TR-4 FORM IS REQUIRED ON THIS PROJECT.1704.7.4 Special inspection of soils investigations, borings and test pits. Boring operations shall…
Technical info
Full details ›PLEASE NOTE A TR-4 FORM IS REQUIRED ON THIS PROJECT.
1704.7.4 Special inspection of soils investigations, borings and test pits. Boring operations shall be subject to continuous special inspection to verify compliance with Section 1802. Soil sample recovery operations for test pits shall be subject to continuous special inspection to verify compliance with Section 1802.Exception: Existing boring, test pit and soil investigation records that have been deemed acceptable to the commissioner in accordance with Section 1802.4.2 are not subject to special inspection.
-
-
TR-5 PILE DRIVING
TR-5 Pile Foundations Drilled Pier Installation
PLEASE NOTE A TR-5 FORM IS REQUIRED FOR THIS PROJECT.1704.8 Pile foundations. A special inspector shall be present when pile foundations are…
Technical info
Full details ›PLEASE NOTE A TR-5 FORM IS REQUIRED FOR THIS PROJECT.
1704.8 Pile foundations. A special inspector shall be present when pile foundations are being installed and during tests. The special inspector shall make and submit to the commissioner records of the installation of each pile and results of load tests. Records shall include the cutoff and tip elevation of each pile relative to a permanent reference. A special inspector shall verify that pile installation procedures are in accordance with Section 1808. -
TR-5 PILE DRIVING
TR-5H Helical Piles (1704.8.5)
TR-5H Helical Pile Special Inspection A helical pile is a deep foundation element consisting of a central steel shaft with one…
Technical info
Full details ›TR-5H Helical Pile Special Inspection
A helical pile is a deep foundation element consisting of a central steel shaft with one or more helical steel plates (flights) welded along its length. Installation is achieved by rotating the pile into the ground using a hydraulic motor, threading it down like a giant screw through soft or unstable soils until the helix plates reach competent bearing strata. Because helical piles are installed by torque rather than impact driving, they produce no vibration, making them the preferred foundation solution in densely developed urban environments where adjacent structures must be protected.
Where Helical Piles Are Used in NYC Construction
Helical piles have become increasingly common across all five boroughs, particularly for:
- Brownstone and rowhouse underpinning in Brooklyn, Harlem, and the West Village — where failing original foundations must be reinforced without disturbing neighboring party walls or landmarked facades
- Landmarked building foundation repairs — where the NYC Landmarks Preservation Commission requires non-destructive methods that do not compromise adjacent historic fabric
- New construction on soft soil sites — in areas underlain by fill, marine clay, or organic deposits (common in lower Manhattan, coastal Queens, and waterfront Brooklyn), where spread footings would require excessive excavation
- Tight urban sites — where crane access for driven or drilled piles is impossible and helical installation equipment can operate in confined spaces
NYC BC 1704.8.5 Special Inspection Requirements
Under NYC Building Code Section 1704.8.5, helical pile installation must be monitored by a special inspector during the entire installation process. The inspector verifies:
- Installation torque — the torque applied during installation is continuously recorded and compared to the design torque specified by the geotechnical engineer of record. Torque correlates directly to the pile’s load-bearing capacity.
- Depth of installation — the pile is advanced to the specified minimum depth and/or until the target torque is achieved and maintained, confirming the helix plates have engaged competent bearing soil
- Pile shaft verticality and alignment — verified against the approved foundation drawings
- Pile cap or bracket connections — the mechanical connection between the helical pile and the structure being supported is confirmed per the approved design
How EZTR1 Conducts the Inspection
EZTR1’s certified TR-5H special inspectors are present on site throughout helical pile installation, maintaining continuous installation logs for each pile — recording torque readings at every foot of advancement. These logs are cross-referenced against the geotechnical report and submitted as part of the TR-5H special inspection report filed directly with the NYC Department of Buildings.
Ready to schedule your helical pile special inspection? Contact EZTR1 to coordinate with your foundation contractor’s installation schedule.
-
TR-7 PHOTOLUMINESCENT REPORT
TR-7 Photoluminescent Exit Path Marking BC 1026.11
PLEASE NOTE A TR-7 FORM IS REQUIRED ON THIS PROJECT.1026.11 Photoluminescent exit path marking. Photoluminescent exit path markings in high-rise buildings subject…
Technical info
Full details ›PLEASE NOTE A TR-7 FORM IS REQUIRED ON THIS PROJECT.
1026.11 Photoluminescent exit path marking. Photoluminescent exit path markings in high-rise buildings subject to Section 403.16 shall be provided in accordance with this section. All exit path markings required herein shall be of an approved photoluminescent material. The markings shall be washable, nontoxic, nonradioactive, and if subjected to fire must be self extinguishing when the flame is removed. Exit path markings shall at a minimum be located:1. On all doors opening to exits, exit passageways, or horizontal exits and shall be marked with the word “EXIT.”
2. Within exit stairs, horizontal extensions in exit stairs, horizontal exits, and exit passagewaysException: Within street-level lobbies where egress direction is immediately discernible.
Required markings for exit paths shall comply with the technical standards for installation and placement in accordance with rules promulgated by the commissioner.
-
TR-8 ENERGY INSPECTIONS
EN-2 Energy Code Analysis (BC 109.3.5)
NYC Energy Code Analysis as required by NYCDOB, limited to small projects, 4000sf or less. Energy code compliance Analysis shall be made to…
Technical info
Full details ›NYC Energy Code Analysis as required by NYCDOB, limited to small projects, 4000sf or less.
Energy code compliance Analysis shall be made to determine compliance with NYC Energy Conservation Code.
Details
per TR-8
Project-specific pricing requiredRequest a Quote -
TR-8 ENERGY INSPECTIONS
TR-1 Energy Code Compliance Inspections (BC 110.3.5)
110.3.5 Energy code compliance inspections.Inspections shall be made to determine compliance with approved construction documents. per TR-8
Technical info
Full details ›110.3.5 Energy code compliance inspections.Inspections shall be made to determine compliance with approved construction documents.
Details
per TR-8
-
TR-8 ENERGY INSPECTIONS
TR-8 Shutoff Dampers (IB2), (IIB2)
1RCNY IB2Not less than 20% of installed automatic or gravity dampers, and a minimum of one of each type, shall be visually…
Technical info
Full details ›1RCNY IB2
Not less than 20% of installed automatic or gravity dampers, and a minimum of one of each type, shall be visually inspected and physically tested for proper operation.1RCNY IIB2
Dampers for stair and elevator shaft vents and other outdoor air intakes and exhaust openings integral to the building envelope shall be visually inspected to verify that such dampers, except where permitted to be gravity dampers, comply with approved construction drawings.
Manufacturer’s literature shall be reviewed to verify that the product has been tested and found to meet the standard.Details
Energy Shutoff Dampers vs. Fire Dampers
A common source of confusion on NYC construction sites is the difference between energy shutoff dampers — which are required under the Energy Conservation Code and inspected during TR-8 — and fire or smoke dampers, which are life-safety devices inspected under separate NYC Fire Code and Mechanical Code requirements. These are different systems with different inspectors and different code sections. TR-8 shutoff damper inspections address energy performance only.
What 1RCNY §IB2 requires for Class 1 buildings (1- and 2-family homes):
The ECC requires that at least 20% of all installed automatic or gravity dampers — with a minimum of one of each type present — be both visually inspected and physically tested for proper operation. Physical testing means the inspector manually operates the damper to confirm it opens and closes as designed, preventing conditioned air from escaping through HVAC ductwork when equipment is off.
Automatic vs. gravity dampers — why the distinction matters:
- Automatic dampers are motor-actuated and close positively when commanded by the building’s HVAC controls. They are required in most Class 2 commercial and high-rise residential applications.
- Gravity dampers close by their own weight when airflow stops. They are lower-cost and permitted in certain residential applications, but must be verified to close fully without binding, warping, or obstructions.
How EZTR1 Conducts the Inspection
EZTR1’s certified progress inspectors identify the full damper inventory on the approved mechanical drawings, select the representative 20% sample, physically cycle each damper, and document results in the TR-8 report filed with the NYC Department of Buildings.
Ready to schedule your TR-8 shutoff damper inspection? Contact EZTR1 to coordinate with your mechanical contractor.
-
TR-8 ENERGY INSPECTIONS
TR-8 Air Barrier – Testing(IA7,IIA7)
Air barrier – testing: Testing must be performed in accordance with section ECC 402.4.1.2 or R402.4.1.3 and shall be accepted if the building…
Technical info
Full details ›Air barrier – testing: Testing must be performed in accordance with section
ECC 402.4.1.2 or R402.4.1.3 and shall be accepted if the building meets the requirements detailed in such section. Test results must be retained in accordance with the provisions of Title 28 Projection factors: Where the energy analysis utilized a projection factor > 0, the projection dimensions of
overhangs, eaves or permanently attached shading devices shall be verified for conformance with approved plans by visual inspection. Air barrier testing: Testing [must] must be performed in accordance with section ECC C402.5.1.3.1 or ASHRAE 90.1 section 5.4.3.1.3, and shall be accepted if the building meets the requirements detailed in such section. Test results shall be retained in accordance with the provisions of Title 28 of the Administrative Code. Testing must be performed by a third-party independent of the contractor and acceptable to the department. -
TR-8 ENERGY INSPECTIONS
TR-8 Air Barrier Continuity Plan Testing/ Inspection(IIA8)
Air barrier continuity plan testing: Each unique air barrier joint or seam must be tested or inspected for compliance. Documentation includes the…
Technical info
Full details ›Air barrier continuity plan testing:
Each unique air barrier joint or seam
must be tested or inspected for
compliance. Documentation includes the
method of test performed on each unique
air barrier joint or seam and the results of
the test. If an air barrier joint or seam has
a deficiency, the deficiency must be
noted, and retested until it complies with
the testing requirements. Test results
must be retained in accordance with the
provisions of Title 28 of the
Administrative Code.
Testing must be performed by a thirdparty independent of the contractor and
acceptable to the department. -
TR-8 ENERGY INSPECTIONS
TR-8 Air Barrier-Visual Inspection(IA6,IIA6)
Air barrier – visual inspection: Openings and penetrations in the building envelope, including site-built fenestration and doors, must be visually inspected to verify that…
Technical info
Full details ›Air barrier – visual inspection: Openings and penetrations in the building envelope, including site-built fenestration and doors, must be visually inspected to verify that they are properly sealed, in accordance with Table 402.4.2. Air sealing and insulation – visual inspection: Openings and penetrations in the building envelope, including site-built fenestration and doors, must be visually inspected to verify that a continuous air barrier around the envelope forms an air-tight enclosure. The progress inspector must visually inspect to verify that materials and/or assemblies have been tested and meet the requirements of the respective standards, or that the building is tested and meets the requirements of the standard, in accordance with the standard(s) cited in the approved plans. -
TR-8 ENERGY INSPECTIONS
TR-8 Air Sealing and Insulation – Testing
1RCNY IA7Testing shall be performed in accordance with section ECC 402.4.2.1 and shall be accepted if the building meets the requirements detailed…
Technical info
Full details ›1RCNY IA7
Testing shall be performed in accordance with section ECC 402.4.2.1 and shall be accepted if the building meets the requirements detailed in such section. Test results shall be retained in accordance with the provisions of Title 28.Details
-
TR-8 ENERGY INSPECTIONS
TR-8 Air Sealing and Insulation – Visual
1RCNY IA6Openings and penetrations in the building envelope, including site-built fenestration and doors, shall be visually inspected to verify that they are…
Technical info
Full details ›1RCNY IA6
Openings and penetrations in the building envelope, including site-built fenestration and doors, shall be visually inspected to verify that they are properly sealed, in accordance with Table 402.4.2.1RCNY IIA6
Openings and penetrations in the building envelope, including site-built fenestration and doors, shall be visually inspected to verify that a continuous air barrier around the envelope forms an air-tight enclosure.
The progress inspector shall visually inspect to verify that materials and/or assemblies have been tested and meet the requirements of the respective standards, or that the building is tested and meets the requirements of the standard, in accordance with the standard(s) citedDetails
-
TR-8 ENERGY INSPECTIONS
TR-8 Air Sealing and Insulation Testing/ Blower Door Test Report
Testing shall be performed in accordance with section ECC 402.4.2.1 and shall be accepted if the building meets the requirements detailed in…
Technical info
Full details ›Testing shall be performed in accordance with section ECC 402.4.2.1 and shall be accepted if the building meets the requirements detailed in such section. Test results shall be retained in accordance with the provisions of Title 28.
The building or dwelling unit shall be tested and verified as having an air leakage rate not exceeding three air changes per hour. Testing shall be conducted in accordance with ASTM E 779 or ASTM E 1827 and reported at a pressure of 0.2 inch w.g. (50 Pascals). Testing shall be performed at any time after creation of all penetrations of the building thermal envelope.
Details
-
TR-8 ENERGY INSPECTIONS
TR-8 Dampers Integral to Building Envelope
1RCNY IB2Not less than 20% of installed automatic or gravity dampers, and a minimum of one of each type, shall be visually…
Technical info
Full details ›1RCNY IB2
Not less than 20% of installed automatic or gravity dampers, and a minimum of one of each type, shall be visually inspected and physically tested for proper operation.1RCNY IIB2
Dampers for stair and elevator shaft vents and other outdoor air intakes and exhaust openings integral to the building envelope shall be visually inspected to verify that such dampers, except where permitted to be gravity dampers, comply with approved construction drawings.
Manufacturer’s literature shall be reviewed to verify that the product has been tested and found to meet the standard.Details
What Makes a Damper Integral to the Building
A damper is considered integral to the building envelope when it is physically installed within an exterior wall, roof assembly, or floor/ceiling assembly at the point where an HVAC duct, shaft, or ventilation opening penetrates the building’s thermal and air boundary. These are not interior zone dampers — they are the last line of defense between the conditioned interior of the building and the outdoor environment.
In NYC construction, this category includes:
- Outdoor air intake dampers — installed where fresh air enters the mechanical system through an exterior wall penetration
- Exhaust air dampers — at the termination point of kitchen, bathroom, or dryer exhaust systems through the building envelope
- Stair and elevator shaft vent dampers — at the top or exterior wall penetrations of shaft enclosures, required to limit stack-effect air movement
- Relief air dampers — at exterior wall openings where pressurized supply air is exhausted to maintain building pressure balance
Under 1RCNY §IIB2 (Class 2 buildings), these dampers must comply with approved construction drawings and be supported by manufacturer’s literature confirming the product has been independently tested to meet the required standard — a higher bar than simple visual inspection.
How EZTR1 Inspects
EZTR1’s certified progress inspectors verify damper location against approved DOB drawings, confirm product compliance documentation is on file, and conduct physical operation checks at each envelope penetration point. All findings are documented in the TR-8 report filed with the NYC Department of Buildings.
Ready to schedule your TR-8 building envelope damper inspection? Contact EZTR1 to coordinate with your construction schedule.
-
-
TR-8 ENERGY INSPECTIONS
TR-8 Duct Leakage Testing
1RCNY IB6Where the air handler and/or some ductwork is in unconditioned space, duct-leakage testing shall be performed either after rough-in or post-construction…
Technical info
Full details ›1RCNY IB6
Where the air handler and/or some ductwork is in unconditioned space, duct-leakage testing shall be performed either after rough-in or post-construction to ensure compliance with ECC 403.2.2. Not less than 20% of such ductwork shall be tested.1RCNY IIB6
For duct systems designed to operate at static pressures in excess of 3 inches w.g. (746 Pa), representative sections, as determined by the progress inspector, totaling at least 25% of the duct area, per ECC 503.2.7.1.3, shall be tested to verify that actual air leakage is below allowable amounts.Details
How Duct Leakage Testing Works
Duct leakage testing uses a calibrated pressurization fan — commonly called a duct blaster — to pressurize the supply or return duct system to a standard test pressure while all registers are sealed. The measured air flow required to maintain that pressure represents the leakage rate of the duct system. A high leakage rate means conditioned air is escaping into unconditioned spaces such as wall cavities, attic chases, or mechanical rooms, directly wasting energy and degrading system performance.
NYC Class 1 vs. Class 2 requirements:
- Class 1 (1RCNY IB6): Applies when the air handler or any portion of the ductwork is located in unconditioned space. Testing may be performed at rough-in (before insulation is installed) or post-construction. A minimum of 20% of affected ductwork must be tested per ECC Section 403.2.2.
- Class 2 (1RCNY IIB6): Applies to duct systems operating at static pressures exceeding 3 inches w.g. (746 Pa). A progress inspector selects representative sections totaling at least 25% of the duct area for testing per ECC Section 503.2.7.1.3.
How EZTR1 Executes and Documents Testing
EZTR1’s certified progress inspectors coordinate duct leakage testing at the appropriate construction phase, witness the pressurization test, and verify that measured leakage rates fall within allowable limits per the approved energy compliance filing. All test results, sampled duct sections, and pass/fail determinations are documented in the TR-8 inspection report filed with the NYC Department of Buildings.
Ready to schedule your TR-8 duct leakage inspection? Contact EZTR1 to coordinate testing at the right construction phase.
-
TR-8 ENERGY INSPECTIONS
TR-8 Duct Plenum and Piping Insulation and Sealing
1RCNY IB5Installed duct and piping insulation shall be visually inspected to verify correct insulation placement and values. Ducts, air handlers, filter boxes…
Technical info
Full details ›1RCNY IB5
Installed duct and piping insulation shall be visually inspected to verify correct insulation placement and values.
Ducts, air handlers, filter boxes and building cavities used as ducts shall be visually inspected for proper sealing.1RCNY IIB5
Installed duct and piping insulation shall be visually inspected to verify proper insulation placement and values.
Joints, longitudinal and transverse seams and connections in ductwork shall be visually inspected for proper sealing.Details
-
TR-8 ENERGY INSPECTIONS
TR-8 Electric Vehicle Service Equipment Requirements(ID3)
Electric vehicle service equipment requirements ]Electric vehicle outlet or conduit and electrical service reserved space must be visually inspected to verify compliance.…
Technical info
Full details ›Electric vehicle service equipment requirements ]Electric vehicle outlet or conduit and electrical service reserved space must be visually inspected to verify compliance. Location [shall]must be noted on the permanent certificate. -
TR-8 ENERGY INSPECTIONS
TR-8 Electrical Energy Consumption (IC1), (IICC1
1RCNY IC1The presence and operation of individual meters or other means of monitoring individual dwelling units shall be verified by visual inspection…
Technical info
Full details ›1RCNY IC1
The presence and operation of individual meters or other means of monitoring individual dwelling units shall be verified by visual inspection for all dwelling units.1RCNY IIC1
The presence and operation of individual meters or other means of monitoring individual apartments shall be verified by visual inspection for all apartments.Details
-
TR-8 ENERGY INSPECTIONS
TR-8 Electrical Metering
1RCNY IC1The presence and operation of individual meters or other means of monitoring individual dwelling units shall be verified by visual inspection…
Technical info
Full details ›1RCNY IC1
The presence and operation of individual meters or other means of monitoring individual dwelling units shall be verified by visual inspection for all dwelling units.1RCNY IIC1
The presence and operation of individual meters or other means of monitoring individual apartments shall be verified by visual inspection for all apartments.Details
Individual Metering in NYC Buildings
Individual electrical metering is a foundational energy accountability measure under New York City’s Energy Conservation Code. By requiring that each dwelling unit or apartment have its own meter or equivalent monitoring device, the ECC ensures that occupants have direct visibility into their energy consumption — which consistently reduces usage compared to buildings where utility costs are bundled into rent.
Class 1 vs. Class 2 application:
- 1RCNY §IC1 (Class 1 — 1- and 2-family homes, townhouses): Each dwelling unit must have an individual meter or monitoring device that is present and operational at the time of the TR-8 progress inspection.
- 1RCNY §IIC1 (Class 2 — multifamily residential, 3 stories and above): Each individual apartment must be separately metered or monitored. This requirement aligns with NYC Local Law 132 (2016), which mandates sub-metering for certain large residential buildings, reinforcing the ECC’s unit-level monitoring requirement.
What EZTR1 Inspects
EZTR1’s certified progress inspectors verify the following during a TR-8 electrical metering inspection:
- Meter presence — individual meters are physically installed and assigned to each unit per the approved electrical drawings
- Operational status — meters are energized, reading correctly, and accessible for verification
- Monitoring alternatives — where smart meters or building energy management systems are used in lieu of individual meters, the inspector confirms the system meets the “other means of monitoring” standard per the approved energy compliance filing
All findings are documented in the TR-8 inspection report filed with the NYC Department of Buildings.
Ready to schedule your TR-8 electrical metering inspection? Contact EZTR1 to confirm compliance before your DOB sign-off.
-
TR-8 ENERGY INSPECTIONS
TR-8 Electrical Motors
1RCNY IIC8Where required by the construction documents for energy code compliance, motor listing or labels shall be visually inspected to verify that…
Technical info
Full details ›1RCNY IIC8
Where required by the construction documents for energy code compliance, motor listing or labels shall be visually inspected to verify that they comply with the respective energy requirements in the construction documents.Details
-
-
TR-8 ENERGY INSPECTIONS
TR-8 Exit Signs
1RCNY IIC6Installed exit signs shall be visually inspected to verify that the label indicates that they do not exceed maximum permitted wattage.…
Technical info
Full details ›1RCNY IIC6
Installed exit signs shall be visually inspected to verify that the label indicates that they do not exceed maximum permitted wattage.Details
-
TR-8 ENERGY INSPECTIONS
TR-8 Exterior Lighting Power
1RCNY IIC4Installed lighting shall be verified for compliance with source efficacy and/or the lighting power allowance by visual inspection of fixtures, lamps,…
Technical info
Full details ›1RCNY IIC4
Installed lighting shall be verified for compliance with source efficacy and/or the lighting power allowance by visual inspection of fixtures, lamps, ballasts and relevant transformers.Details
-
TR-8 ENERGY INSPECTIONS
TR-8 Fenestration Areas
1RCNY IA5Dimensions of windows, doors and skylights shall be verified by visual inspection. 1RCNY IIA5Dimensions of windows, doors and skylights shall be…
Technical info
Full details ›1RCNY IA5
Dimensions of windows, doors and skylights shall be verified by visual inspection.1RCNY IIA5
Dimensions of windows, doors and skylights shall be verified by visual inspection.What Is Fenestration Area Compliance in NYC Construction?
Fenestration area compliance is a required component of New York City’s Energy Conservation Code (ECC) inspection process, and it applies to most new residential and mixed-use construction projects in the five boroughs. Under 1RCNY §IA5 and §IIA5, the physical dimensions of all installed windows, exterior doors, and skylights must be measured and verified against the approved construction drawings during a TR-8 energy inspection.
This requirement exists because the total glazed area of a building — expressed as a percentage of the gross wall area — directly affects how much heat is gained or lost through the building envelope. Oversized fenestration increases thermal loads, while undersized openings may not meet ventilation or natural light minimums. Both conditions can result in a failed inspection and a DOB stop-work order.
Which buildings are affected? Fenestration area verification is required for:
- Class 1 buildings (1- and 2-family homes, townhouses) under 1RCNY IA5
- Class 2 buildings (multifamily residential, three stories and above) under 1RCNY IIA5
- New construction and gut-renovated buildings subject to full ECC compliance
How EZTR1 Conducts the Inspection Our certified special inspectors verify fenestration dimensions on-site using field measurements cross-referenced against the approved DOB construction drawings. We confirm that the rough opening sizes, installed frame dimensions, and total fenestration area ratios are consistent with the energy compliance documentation submitted to the DOB. All findings are documented in our TR-8 inspection report, which is filed directly with the Department of Buildings.
Ready to schedule your TR-8 fenestration area inspection? Contact EZTR1 today to confirm compliance before your next DOB inspection milestone.
Details
-
TR-8 ENERGY INSPECTIONS
TR-8 Fenestration Door U-Factor and Product Rating(IA3)(IIA3)
1RCNY IA3U-factors of installed fenestration shall be verified by visual inspection for conformance with the U-factors identified in the construction drawings, either…
Technical info
Full details ›1RCNY IA3
U-factors of installed fenestration shall be verified by visual inspection for conformance with the U-factors identified in the construction drawings, either by verifying the manufacturer’s NFRC labels or, where not labeled, using the ratings in ECC Tables 303.1.3(1) and (2).1RCNY IIA3
U-factors and SHGC values of installed fenestration shall be visually inspected for conformance with the U-factors and SHGC values identified in the construction drawings by verifying the manufacturer’s NFRC labels or, where not labeled, using the ratings in ECC Tables 303.1.3(1), (2) and (3). Where ASHRAE 90.1 is used, visible light transmittance values shall also be verified.Details
What the NFRC Label Tells Your NYC Inspector
The NFRC (National Fenestration Rating Council) label is the primary product-level document your special inspector checks during a TR-8 fenestration inspection in New York City. Affixed directly to the window or door unit, the label certifies the product’s tested U-factor and Solar Heat Gain Coefficient (SHGC) as independently verified by an accredited simulation laboratory — not just claimed by the manufacturer.
What EZTR1 inspectors verify on the label:
- U-factor and SHGC values match the fenestration product schedule in the approved DOB construction drawings
- The NFRC certification mark is present and legible on the installed unit
- The product series or model number on the label corresponds to the specified product — substitutions require a revised DOB filing
The most common NYC DOB inspection finding: Labels removed by glaziers during installation, or products swapped in the field without updating the approved plans. In both cases, the inspector must reference ECC Tables 303.1.3(1) and (2) for Class 1 buildings, or Tables 303.1.3(1), (2), and (3) for Class 2 buildings, to establish a fallback rating for the unlabeled unit.
When a product cannot be rated through either the label or the ECC Tables, the installation fails the TR-8 inspection and a corrective action report is filed with the Department of Buildings.
Ready to confirm your windows and doors are code-compliant before your DOB inspection? Contact EZTR1 to schedule your TR-8 fenestration product rating inspection today.
-
TR-8 ENERGY INSPECTIONS
TR-8 Fenestration Ratings for Air Leakage
1RCNY IA4Windows, skylights and sliding glass doors, except site-built windows, skylights and doors, shall be visually inspected to verify that installed assemblies…
Technical info
Full details ›1RCNY IA4
Windows, skylights and sliding glass doors, except site-built windows, skylights and doors, shall be visually inspected to verify that installed assemblies are listed and labeled to the referenced standard.1RCNY IIA4
Windows and sliding or swinging door assemblies, except site-built windows and/or doors, shall be visually inspected to verify that installed assemblies are listed and labeled by the manufacturer to the referenced standard.
For curtain wall, storefront glazing, commercial entrance doors and revolving doors, the testing reports shall be reviewed to verify that the installed assembly complies with the standard cited in the approved plans.Details
-
TR-8 ENERGY INSPECTIONS
TR-8 Fenestration Thermal Values and Ratings
1RCNY IA3U-factors of installed fenestration shall be verified by visual inspection for conformance with the U-factors identified in the construction drawings, either…
Technical info
Full details ›1RCNY IA3
U-factors of installed fenestration shall be verified by visual inspection for conformance with the U-factors identified in the construction drawings, either by verifying the manufacturer’s NFRC labels or, where not labeled, using the ratings in ECC Tables 303.1.3(1) and (2).1RCNY IIA3
U-factors and SHGC values of installed fenestration shall be visually inspected for conformance with the U-factors and SHGC values identified in the construction drawings by verifying the manufacturer’s NFRC labels or, where not labeled, using the ratings in ECC Tables 303.1.3(1), (2) and (3). Where ASHRAE 90.1 is used, visible light transmittance values shall also be verified.
Details
Beyond the Label: Understanding Whole-Assembly The
While verifying NFRC labels confirms a product’s rated performance, the TR-8 inspection for fenestration thermal values goes further — it evaluates how the installed fenestration system performs as part of the complete building envelope assembly under NYC’s Energy Conservation Code (ECC).
The ECC Tables 303.1.3(1), (2), and (3) establish maximum allowable U-factors and minimum Solar Heat Gain Coefficient (SHGC) thresholds for the entire glazing system, not just individual products. This means the thermal performance of the frame, spacer, glazing layers, and installation method must collectively meet code — even if each individual component is rated correctly on its label.
Where this matters most in NYC construction:
- High-rise curtain wall systems — where the framing system’s thermal bridging can significantly degrade the assembly U-factor below what individual product ratings suggest
- Mixed-use buildings using ASHRAE 90.1 — which additionally requires verification of Visible Light Transmittance (VLT) values
- Gut-renovated brownstones — where new fenestration is installed in existing masonry openings, requiring field verification that thermal performance matches the energy compliance documents filed with the DOB
Relationship to blower door and air infiltration testing: A fenestration assembly that passes U-factor verification but fails air sealing can undermine the building’s overall thermal envelope performance. EZTR1 inspectors flag installation deficiencies — such as missing sill flashing, inadequate sealant at jambs, or thermal bridges at rough openings — that affect the assembly’s real-world thermal performance beyond what the label alone confirms.
Need a TR-8 thermal values inspection for your NYC project? Contact EZTR1 to schedule with a certified special inspector.
-
TR-8 ENERGY INSPECTIONS
TR-8 Fireplaces
1RCNY IB1Provision of combustion air and tight-fitting fireplace doors shall be verified by visual inspection. 1RCNY IIB1Provision of combustion air and tight-fitting…
Technical info
Full details ›1RCNY IB1
Provision of combustion air and tight-fitting fireplace doors shall be verified by visual inspection.1RCNY IIB1
Provision of combustion air and tight-fitting fireplace doors shall be verified by visual inspection.Details
TR-8 Fireplace Inspection
Fireplaces are one of the most significant sources of uncontrolled air infiltration in New York City buildings. When a fireplace damper is left open, missing, or improperly fitted, it functions as a direct opening in the building envelope — allowing heated or cooled interior air to escape and unconditioned outdoor air to enter freely. This is why the NYC Energy Conservation Code specifically requires fireplace compliance to be verified during a TR-8 progress inspection.
What the NYC Energy Code Requires
Under 1RCNY §IB1 (Class 1 — 1- and 2-family homes and townhouses) and 1RCNY §IIB1 (Class 2 — multifamily residential), two fireplace elements must be verified by visual inspection:
- Provision of combustion air — the fireplace must have a dedicated, code-compliant source of combustion air that does not draw from the conditioned living space, reducing the depressurization of the building interior during fireplace use
- Tight-fitting fireplace doors — glass or metal doors must be present, properly installed, and capable of closing fully against the firebox face to restrict air infiltration when the fireplace is not in use
What EZTR1 Inspects
EZTR1’s certified special inspectors verify both elements on-site against the approved DOB construction documents:
- Damper presence, condition, and operation (open/close mechanism intact)
- Tight-fitting door installation — no visible gaps at the frame or sweep
- Combustion air opening location, sizing, and compliance with the energy filing
All findings are documented in the TR-8 inspection report filed with the NYC Department of Buildings.
Ready to schedule your TR-8 fireplace inspection? Contact EZTR1 to confirm compliance before your DOB sign-off.
-
TR-8 ENERGY INSPECTIONS
TR-8 HVAC R and Service Water Heating System Control
1RCNY IB4System controls shall be inspected to verify that each dwelling is provided with at least one individual programmable thermostat with capabilities…
Technical info
Full details ›1RCNY IB4
System controls shall be inspected to verify that each dwelling is provided with at least one individual programmable thermostat with capabilities as described in ECC 403.1.1, and that such controls are set and operate as specified in ECC 403.1.1.
Controls for supplementary electric-resistance heat pumps shall be inspected to verify that such controls prevent supplemental heat operation when the heat pump compressor can meet the heating load.
Controls for snow- and ice-melting systems and pools shall be inspected for proper operation. Not less than 20% or one of each control type, whichever is more, shall be inspected.1RCNY IIB4
No less than 20% of each type of required controls and economizers shall be verified by visual inspection and tested for functionality and proper operation. Such controls shall include, but are not limited to:
• Thermostatic
• Set point overlap restriction
• Off-hour
• Shutoff damper
• Snow-melt system
• Demand control systems
• Outdoor heating systems
• Zones
• Economizers
• Air systems
• Variable air volume fan
• Hydronic systems
• Heat rejection equipment fan speed
• Complex mechanical systems serving multiple zones
• Ventilation
• Energy recovery systems
• Hot gas bypass limitation
• Temperature
• Service water heating
• Hot water system
• Pool heater and time switches
• Exhaust hoods
• Radiant heating systems.Details
-
TR-8 ENERGY INSPECTIONS
TR-8 HVAC R and Service Water piping design &insulation
HVAC-R and service water piping design and insulation : Installed piping insulation must be visuall inspected to verify proper insulation placement and values.…
Technical info
Full details ›HVAC-R and service water piping design and insulation : Installed piping insulation must be visuall inspected to verify proper insulation placement and values. Service hot water distribution systems
must be inspected to verify the supply of heated water. HVAC and service water piping design and insulation : Installed piping insulation [shall]must be visually inspected to verify correct
insulation placement and values. [ Service hot water distribution systems must be inspected to verify the supply of heated water.Details
-
TR-8 ENERGY INSPECTIONS
TR-8 HVAC-R and Service Water Heating Equipment
1RCNY IB3Heating and cooling equipment shall be verified by visual inspection for proper sizing. Pool heaters and covers shall be verified by…
Technical info
Full details ›1RCNY IB3
Heating and cooling equipment shall be verified by visual inspection for proper sizing. Pool heaters and covers shall be verified by visual inspection.1RCNY IIB3
Equipment sizing, efficiencies and other performance factors of all major equipment units, as determined by the applicant of record, and no less than 15% of minor equipment units, shall be verified by visual inspection and, where necessary, review of manufacturer’s data.
Pool heaters and covers shall be verified by visual inspection.Details
-
TR-8 ENERGY INSPECTIONS
TR-8 Insulation Placement and R Values
1RCNY IA2Installed insulation for each component of the conditioned space envelope and at junctions between components shall be visually inspected to ensure…
Technical info
Full details ›1RCNY IA2
Installed insulation for each component of the conditioned space envelope and at junctions between components shall be visually inspected to ensure that the R-values are marked, that such R-values conform to the R-values identified in the construction documents and that the insulation is properly installed. Certifications for unmarked insulation shall be similarly visually inspected.1RCNY IIA2
Installed insulation for each component of the conditioned space envelope and at junctions between components shall be visually inspected to ensure that the R-values are marked, that such R-values conform to the R-values identified in the construction documents and that the insulation is properly installed. Certifications for unmarked insulation shall be similarly visually inspected.Details
-
TR-8 ENERGY INSPECTIONS
TR-8 Interior Lighting Power
1RCNY IIC3Installed lighting shall be verified for compliance with the lighting power allowance by visual inspection of fixtures, lamps, ballasts and transformers.…
Technical info
Full details ›1RCNY IIC3
Installed lighting shall be verified for compliance with the lighting power allowance by visual inspection of fixtures, lamps, ballasts and transformers.Details
-
TR-8 ENERGY INSPECTIONS
TR-8 Lighting Controls
1RCNY IIC5Each type of required lighting controls, including: • occupant sensors • manual interior lighting controls • light-reduction controls • automatic lighting…
Technical info
Full details ›1RCNY IIC5
Each type of required lighting controls, including:
• occupant sensors
• manual interior lighting controls
• light-reduction controls
• automatic lighting shut-off
• daylight zone controls
• sleeping unit controls
• exterior lighting controls
shall be verified by visual inspection and tested for functionality and proper operation.Details
-
TR-8 ENERGY INSPECTIONS
TR-8 Lighting in Dwelling Units
1RCNY IC2Lamps in permanently installed lighting fixtures shall be visually inspected to verify compliance with high-efficacy requirements. 1RCNY IIC2Lamps in permanently installed…
Technical info
Full details ›1RCNY IC2
Lamps in permanently installed lighting fixtures shall be visually inspected to verify compliance with high-efficacy requirements.1RCNY IIC2
Lamps in permanently installed lighting fixtures shall be visually inspected to verify compliance with high-efficacy requirements.Details
What NYC Inspectors Actually Check
Under New York City’s Energy Conservation Code, “high-efficacy” refers to lamps that meet a minimum luminous efficacy threshold — measured in lumens per watt — as defined in ECC Section 404. In practice, this means LED lamps and fixtures, or compact fluorescent lamps (CFLs) that meet the threshold. Incandescent and halogen lamps in permanently installed fixtures do not qualify and will result in a failed TR-8 inspection.
Class 1 vs. Class 2 scope:
- 1RCNY §IC2 (Class 1 — 1- and 2-family homes, townhouses): All permanently installed lighting fixtures in the dwelling unit must use high-efficacy lamps. This includes recessed cans, ceiling mounts, under-cabinet lighting, and bathroom vanity fixtures.
- 1RCNY §IIC2 (Class 2 — multifamily residential, 3 stories and above): The same high-efficacy requirement applies to permanently installed fixtures in each individual dwelling unit. Common area and corridor lighting is addressed separately under other code sections.
Common NYC DOB inspection failures:
- Non-compliant lamps installed by an electrician or contractor after the approved fixtures were set
- Recessed downlights fitted with incandescent retrofit bulbs instead of LED modules
- Fixtures missing manufacturer labels confirming high-efficacy compliance
How EZTR1 Inspects
EZTR1’s certified special inspectors perform a visual inspection of all permanently installed lighting fixtures, confirming lamp type and efficacy compliance against the approved construction documents. Findings are documented in the TR-8 inspection report filed with the NYC DOB.
Ready to schedule your TR-8 lighting inspection? Contact EZTR1 before your final DOB sign-off.
-
TR-8 ENERGY INSPECTIONS
TR-8 Loading Deck Weather Seals
1RCNY IIA8Weatherseals at loading docks shall be visually verified.
Technical info
Full details ›1RCNY IIA8
Weatherseals at loading docks shall be visually verified.Details
-
TR-8 ENERGY INSPECTIONS
TR-8 Maintenance Information
1RCNY ID1Maintenance manuals for equipment and systems requiring preventive maintenance shall be reviewed for applicability to installed equipment and systems before such…
Technical info
Full details ›1RCNY ID1
Maintenance manuals for equipment and systems requiring preventive maintenance shall be reviewed for applicability to installed equipment and systems before such manuals are provided to the owner.
Labels required for such equipment or systems shall be inspected for accuracy and completeness.1RCNY IID1
Maintenance manuals for mechanical, service hot water and electrical equipment and systems requiring preventive maintenance shall be reviewed for applicability to installed equipment and systems before such manuals are provided to the owner. Labels required for such equipment or systems shall be inspected for accuracy and completeness.Details
-
TR-8 ENERGY INSPECTIONS
TR-8 Permanent Certificate
1RCNY ID2The installed permanent certificate shall be visually inspected for location, completeness and accuracy.
Technical info
Full details ›1RCNY ID2
The installed permanent certificate shall be visually inspected for location, completeness and accuracy.Details
-
TR-8 ENERGY INSPECTIONS
TR-8 Projection Factors
1RCNY IIA7Where the energy analysis utilized a projection factor > 0, the projection dimensions of overhangs, eaves or permanently attached shading devices…
Technical info
Full details ›1RCNY IIA7
Where the energy analysis utilized a projection factor > 0, the projection dimensions of overhangs, eaves or permanently attached shading devices shall be verified for conformance with approved plans by visual inspection.Details
-
TR-8 ENERGY INSPECTIONS
TR-8 Protection of Foundation Insulation
1RCNY IA1Insulation shall be visually inspected to verify proper protection where applied to the exterior of basement or cellar walls, crawl-space walls…
Technical info
Full details ›1RCNY IA1
Insulation shall be visually inspected to verify proper protection where applied to the exterior of basement or cellar walls, crawl-space walls and/or the perimeter of slab-on-grade floors.1RCNY IIA1
Insulation shall be visually inspected to verify proper protection where applied to the exterior of basement or cellar walls, crawl-space walls and/or the perimeter of slab-on-grade floors.Details
Why Foundation Insulation Needs Protection
Exterior foundation insulation is one of the most effective tools for reducing heat loss through a building’s below-grade envelope, but the insulation itself is vulnerable to UV degradation, physical damage from backfill and landscaping, and moisture infiltration if left exposed. NYC’s Energy Conservation Code requires that any insulation applied to the exterior of basement or cellar walls, crawl-space walls, or the perimeter of slab-on-grade floors must be physically protected — and that protection must be verified by visual inspection during the TR-8 progress inspection.
What “proper protection” means in practice:
Accepted protection methods in NYC construction include:
- Cementitious stucco or parging applied over foam board above grade
- Rigid cement board or cementboard panels for above-grade exposed sections
- HDPE drainage board or dimple mat used in below-grade applications
- Aluminum or galvanized metal flashing at the insulation termination point
Common insulation types requiring protection include extruded polystyrene (XPS) and expanded polystyrene (EPS) rigid foam boards, both of which degrade rapidly when exposed to sunlight or physical impact without a protective covering.
Class 1 vs. Class 2 application: Both 1RCNY §IA1 (Class 1 — 1- and 2-family homes) and §IIA1 (Class 2 — multifamily residential) require the same visual inspection. The requirement applies equally to new construction and to gut-renovated buildings where the foundation assembly has been altered.
Ready to schedule your TR-8 foundation insulation inspection? Contact EZTR1 to confirm compliance before your next DOB inspection milestone.
-
TR-8 ENERGY INSPECTIONS
TR-8 Solar Ready Requirements (ID3)
Technical info
Full details ›Technical details for this inspection are being reviewed. Contact AKS to confirm the inspection requirements for your project. Contact AKS.
-
TR-8 ENERGY INSPECTIONS
TR-8 Tandem Wiring
1RCNY IIC7Tandem wiring shall be tested for functionality.
-
TR-8 ENERGY INSPECTIONS
TR-8 Ventilation and Air Distribution System(IB2)
Ventilation and air distribution system: Ventilation system must be verified to comply with the ERV/HRV requirements or balanced ventilation system. Whole-house ventilation fan…
Technical info
Full details ›Ventilation and air distribution system: Ventilation system must be verified to comply with the ERV/HRV requirements or balanced ventilation system. Whole-house ventilation fan efficacy must be verified by visual inspection. Not less than 20% of installed automatic or gravity dampers, and a minimum of one of each type, must be visually inspected and physically tested for proper operation. Details
-
TR-8 ENERGY INSPECTIONS
TR-8 Vestibules
1RCNY IIA9Required entrance vestibules shall be visually inspected for proper operation. TR-8 Vestibule Inspection A vestibule is […]
Technical info
Full details ›1RCNY IIA9
Required entrance vestibules shall be visually inspected for proper operation.Details
TR-8 Vestibule Inspection
A vestibule is an enclosed entry buffer zone — typically a small anteroom or airlock between an exterior door and the interior of a building — designed to prevent conditioned air from escaping every time the building entrance is used. Under New York City’s Energy Conservation Code, vestibules are a mandatory energy conservation measure for certain building types, and their proper installation and operation must be verified during a TR-8 progress inspection.
What the NYC Energy Code Requires
Under 1RCNY §IA2 (Class 1 buildings — 1- and 2-family homes and townhouses) and 1RCNY §IIA2 (Class 2 buildings — multifamily residential three stories and above), vestibules must be visually inspected for proper operation. This means the inspector confirms that the vestibule functions as intended: both doors do not open simultaneously, the space is fully enclosed, and conditioned air cannot bypass directly from interior to exterior in a single door-open event.
Which Buildings Are Affected
Vestibule requirements typically apply to:
- New multifamily residential buildings with heated lobby entries
- Mixed-use buildings with ground-floor commercial space
- High-occupancy buildings where frequent entry and exit creates significant infiltration load
What EZTR1 Inspects
EZTR1’s certified special inspectors verify the following during a TR-8 vestibule inspection:
- Door gap and self-closing mechanisms — both inner and outer doors must self-close and latch properly, with no excessive gaps at the door sweep, jamb, or threshold
- Air lock integrity — the vestibule must be fully enclosed on all sides, with no open passages that bypass the airlock function
- Heating provisions — where required by the approved construction documents, the inspector confirms that heating elements within the vestibule are present and operational per the energy compliance filing
All findings are documented in the TR-8 inspection report and filed directly with the NYC Department of Buildings.
Ready to schedule your TR-8 vestibule inspection? Contact EZTR1 to confirm your building’s energy compliance before your next DOB milestone.
-
Special Inspections
Adhesive-Based Solar Pedestal Bonding Systems
Project-specific review and pricing required.
Technical info
Full details ›Code section: BC 1705.1.1 (2022); BB #2025-010
Work type(s): SL
Project-specific review and pricing are required for this inspection.
Project-specific pricing requiredRequest a Quote -
Special Inspections
Alternative Materials – OTCR Buildings Bulletin
Project-specific review and pricing required.
Technical info
Full details ›Code section: BC 1704.14 (2014); BC 1705.1.1 (2022)
Work type(s): PL, SP, SD, AN, SF, SG, GC, MS, BE, ST, FO, EA, SOE, PMM, SC, FN, SH, SF
Project-specific review and pricing are required for this inspection.
Project-specific pricing requiredRequest a Quote -
Special Inspections
Combustible Exterior Wall Coverings
Project-specific review and pricing required.
Technical info
Full details ›Code section: BC 1705.16 (2022)
Work type(s): GC, FO
Project-specific review and pricing are required for this inspection.
Project-specific pricing requiredRequest a Quote -
Special Inspections
Construction Operations Influencing Adjacent Structures
Technical info
Full details ›Technical details for this inspection are being reviewed. Contact AKS to confirm the inspection requirements for your project. Contact AKS.
-
Special Inspections
Construction Utilizing CLT or SCL Type IV
Technical info
Full details ›Technical details for this inspection are being reviewed. Contact AKS to confirm the inspection requirements for your project. Contact AKS.
-
Special Inspections
CPVC for water recycling distribution piping systems
Project-specific review and pricing required.
Technical info
Full details ›Code section: BC 1705.1.1 (2022); BB #2011-021
Work type(s): PL, SC
Project-specific review and pricing are required for this inspection.
Project-specific pricing requiredRequest a Quote -
Special Inspections
Designated Seismic System
Technical info
Full details ›Technical details for this inspection are being reviewed. Contact AKS to confirm the inspection requirements for your project. Contact AKS.
-
Special Inspections
Exhaust and Vent Systems in Plenums and Ducts
Technical info
Full details ›Technical details for this inspection are being reviewed. Contact AKS to confirm the inspection requirements for your project. Contact AKS.
-
Special Inspections
Fuel-Oil Storage and Fuel-Oil Piping Systems
Project-specific review and pricing required.
Technical info
Full details ›Code section: BC 1704.17 (2014); BC 1705.22 (2022)
Work type(s): PL, AN, BE*
Project-specific review and pricing are required for this inspection.
Project-specific pricing requiredRequest a Quote -
Special Inspections
Non Potable Water Systems
Technical info
Full details ›Technical details for this inspection are being reviewed. Contact AKS to confirm the inspection requirements for your project. Contact AKS.
-
Special Inspections
Open-Web Steel Joists and Joist Girders
Technical info
Full details ›Technical details for this inspection are being reviewed. Contact AKS to confirm the inspection requirements for your project. Contact AKS.
-
Special Inspections
Polypropylene (“PP”) Piping Systems
Project-specific review and pricing required.
Technical info
Full details ›Code section: BC 1705.1.1 (2022); BB #2015-020
Work type(s): PL, SC
Project-specific review and pricing are required for this inspection.
Project-specific pricing requiredRequest a Quote -
Special Inspections
Post-installed Anchors in Masonry
Project-specific review and pricing required.
Technical info
Full details ›Code section: BC 1705.1.1 (2022); BB #2016-005
Work type(s): ST, SC
Project-specific review and pricing are required for this inspection.
Project-specific pricing requiredRequest a Quote -
Special Inspections
Prefabricated Parallel Chord Wood Trusses
Project-specific review and pricing required.
Technical info
Full details ›Code section: BC 1705.1.1 (2022); BB #2012-004
Work type(s): ST, SC
Project-specific review and pricing are required for this inspection.
Project-specific pricing requiredRequest a Quote -
Special Inspections
Prestressed Rock and Soil Anchors
Technical info
Full details ›Technical details for this inspection are being reviewed. Contact AKS to confirm the inspection requirements for your project. Contact AKS.
-
Special Inspections
Seismic Resistance of Access Floors
Technical info
Full details ›Technical details for this inspection are being reviewed. Contact AKS to confirm the inspection requirements for your project. Contact AKS.
-
Special Inspections
Seismic Resistance of Plumbing, Mechanical, Fuel Gas, and Electrical Components
Technical info
Full details ›Technical details for this inspection are being reviewed. Contact AKS to confirm the inspection requirements for your project. Contact AKS.
-
Special Inspections
Seismic Resistance of Storage Racks
Technical info
Full details ›Technical details for this inspection are being reviewed. Contact AKS to confirm the inspection requirements for your project. Contact AKS.
-
Special Inspections
Tenant Protection Plan Weekly Inspection Compliance
TPP WEEKLY INSPECTION PRICE IS PER INSPECTION. A WEEKLY INSPECTION IS REQUIRED. (As per 2022 NYCBC, Inspection is required 72 hours…
Technical info
Full details ›TPP WEEKLY INSPECTION
PRICE IS PER INSPECTION. A WEEKLY INSPECTION IS REQUIRED.
(As per 2022 NYCBC, Inspection is required 72 hours prior to construction start date, plus once weekly during the entire construction period), THE OWNER IS RESPONSIBLE TO AUTHORIZE AND PAY FOR, MINIMUM 48 HOUR PRIOR TO SCHEDULING, ALL INSPECTIONS DURING THE ENTIRE CONSTRUCTION PERIOD. AKS WILL NOT ATTEND WEEKLY INSPECTION WITHOUT PRIOR PAYMENT AND IS NOT RESPONSIBLE FOR DOB VIOLATIONS ISSUED DUE TO LAPSE IN INSPECTION DUE TO NON-PAYMENT. ADDITIONAL WEEKLY INSPECTIONS CAN BE ALWAYS BE SCHEDULED ON LINE AT www.EZTR1.com
A Tenant Protection Plan (TPP) outlines what steps the contractor and owner will take to protect tenants living in buildings under construction/renovation to avoid or limit service disruptions and mitigate the negative impacts of construction.
Prior to obtaining a construction permit, a Registered Design Professional must submit a TPP if there is at least one occupied dwelling unit. Each construction permit requires its own TPP that outlines tenant protections specific to that scope of work. The elements of the TPP may vary depending on the nature and scope of the work, but at a minimum shall make detailed and specific provisions for:
- Egress. Clarify how adequate egress will be maintained during construction.
- Fire Safety. Identify safety measures to maintain fire safety during construction.
- Health Requirements. Specify methods to be used for dust control, disposal of construction debris, pest control and maintenance of sanitary facilities. Owners must include a statement certifying compliance with applicable laws and filings relating to lead and asbestos.
- Compliance with Housing Standards. Demonstrate compliance with the New York City Housing Maintenance Code, and New York State Multiple Dwelling Law shall be strictly observed.
- Structural Safety. Identify specific measures to maintain structural stability during construction.
- Noise Restrictions. Identify the specific means and methods used to limit noise to acceptable levels in accordance with the NYC Noise Control Code.
- Maintaining Essential Services. Describe specific means and methods to be used to maintain heat, hot water, cold water, gas, electricity, or other utility services, in accordance with the NYC Housing Maintenance Code. Specify if a disruption of any such service is anticipated during the work, the expected duration of such disruption, the means and methods that will be taken to minimize such disruption, including the provision of sufficient alternatives for such service during the disruption. Notification of the disruption must be given to all affected occupants of occupied dwelling units.
1705.26.1 Inspection frequency.
Special inspections shall be performed throughout the duration of the tenant protection plan at sufficient periodic intervals to verify compliance with the tenant protection plan throughout the course of work. At a minimum, inspections shall be performed:
1. Prior to the start of construction and/or demolition to document conditions prior to work;
2. At the start of construction and/or demolition;
3. Once per week during construction and/or demolition;
4. After a tenant protection plan violation has been issued to verify that the violation was corrected;
5. When the location of the alteration or construction operations performed in conjunction with the tenant protection plan has moved to another location; and
6. Whenever construction or demolition operations have changed, requiring changes in methods of protection.
1705.26.2 Reporting.
A written record of the special inspections performed for the tenant protection plan shall be maintained in a log prepared by the special inspector. The log shall include an entry for each inspection and shall indicate that the alteration or construction operation is being performed in accordance with the tenant protection plan. Copies of the special inspection log book shall be maintained at the job site, and at the office of the special inspector, and shall be available for use and review at all reasonable times, until the work subject to special inspection is complete.
-